Powered by GoogleTranslate

Inspection Detail

Inspection: 112067152 - Loma Linda University

Inspection Information - Office: San Bernardino District Office

 

Inspection Nr: 112067152
Report ID: 0950633
Date Opened: 08/09/1991

Site Address:
Loma Linda University
11040 Taylor Ct
Loma Linda, CA 92354

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:8221

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/03/1991

Emphasis:

Case Closed: 10/09/1991


Related Activity
Type Activity Nr Safety Health
Accident 361267834
Complaint 75359836 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 4 5
Current Violations 1 4 5
Initial Penalty $2,500 $0 $0 $0 $0 $2,500
Current Penalty $2,500 $0 $0 $0 $0 $2,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A 09/25/1991 09/25/1991 $0 $0 $0 -  
2. 01002 Other 2811 09/25/1991 09/25/1991 $0 $0 $0 -  
3. 01003 Other 2714 A 09/25/1991 09/25/1991 $0 $0 $0 -  
4. 01004 Other 2940 D01 09/25/1991 09/25/1991 $0 $0 $0 -  
5. 02001 Serious 23200007 A 09/25/1991 09/25/1991 $2,500 $2,500 $0 -  

Investigation Summary

Investigation Nr: 170193353
Event: 08/07/1991
BURN - FAILURE OF UNDERRATED TEST EQUIPMENT

A power plant operator was working in a high voltage switchgear room. The employee had been assigned the task of installing earthquake clips inside the metal-clad, 4160-volt switchgear. The employee opened the rear of the bus section, exposing the bus and current transformers. The employee believed the current transformers to be step-down transformers. He obtained a tester rated at 600 volts and applied it to the current transformer terminals. The tester failed, and the ensuing electric arc burned the employee, who became engulfed in flames. The employee was severely burned on his arms, torso, and face and was hospitalized for his injuries.

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, LOCKOUT, TEST EQUIPMENT, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 112067152 Hospitalized injury Burn/Scald(Heat) Power plant operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.