Inspection Detail
Inspection: 112065537 - The Dca Co.
Inspection Information - Office: Long Beach District Office
Site Address:
The Dca Co.
633 Baldwin Park Blvd.
Industry, CA 91746
Mailing Address:
, , 00000
Union Status: Union
SIC:2041
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/24/1992
Emphasis:
Case Closed: 03/25/1992
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361340417 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 3203 B01 | 02/24/1992 | 03/24/1992 | $0 | $0 | $0 | - | ||
| 2. | 01002 | Other | 3203 B02 | 02/24/1992 | 03/24/1992 | $0 | $0 | $0 | - | ||
| 3. | 01003 | Other | 25400003 | 02/24/1992 | 03/24/1992 | $0 | $0 | $0 | - | ||
| 4. | 01004 | Other | 23400001 | 02/24/1992 | 02/19/1992 | $0 | $0 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS ENERGIZING A MIXER AT A FLOUR MILL BY CLOSING A 600-VOLT, 100-AMPERE, 25/50-HORSEPOWER SWITCH MANUFACTURED BY BULLDOG ELECTRICAL PRODUCTS (CATALOGUE NO. V7E3603). AN ELECTRICAL FAULT OCCURRED INSIDE THE SWITCH, BETWEEN TWO OF THE PHASE POLES AND THE GROUNDED METAL ENCLOSURE; AND THE ENSUING ELECTRIC ARC BURNED THE EMPLOYEE'S RIGHT ARM AND FACE. HE WAS TREATED AT A LOCAL HOSPITAL FOR SECOND DEGREE BURNS AND RELEASED. UPON INSPECTION, THE SWITCH WAS FOUND TO BE BURNED BELOW THE PANELBOARD. HOWEVER, THE INSPECTION FOUND NO EVIDENCE OF FLOUR DUST IN THAT SWITCH OR IN OTHER SWITCHES IN THE PANELBOARD. (THE PANELBOARD WAS LOCATED IN A ROOM WITH A SELF-CLOSING DOOR, AND THE ONLY TIME DUST COULD ENTER WAS WHEN THE DOOR WAS OPENED. THE ELECTRICAL FAULT WAS, THEREFORE, APPARENTLY THE RESULT OF A MALFUNCTION IN THE SWITCH.)
Keywords: BURN, ELECTRIC ARC, ELECTRICAL, ELECTRIC SWITCH, E GI VII, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 112065537 | Non Hospitalized injury | Burn/Scald(Heat) | Food batchmakers |
Translate