Powered by GoogleTranslate

Inspection Detail

Inspection: 112038500 - Don Hegge Electric

Inspection Information - Office: San Bernardino District Office

 

Inspection Nr: 112038500
Report ID: 0950633
Date Opened: 07/27/1990

Site Address:
Don Hegge Electric
73060 Broadmoor Dr.
Thousand Palms, CA 92276

Mailing Address:
4639 Sunny Dunes, Palm Springs, CA 92262

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/04/1990

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 12/19/1990


Related Activity
Type Activity Nr Safety Health
Accident 361306475
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23950050 A 12/20/1990 12/04/1990 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 170194138
Event: 09/26/1990
ELECTRIC SHOCK - GROUND FAULT IN MOBILE HOME WIRING

An electrical contractor had been hired by a mobile home owner to determine why the owner was receiving electric shocks from the outside piping. An electrician with about 4 years of experience was assigned the job. The employee determined that the trailer frame and the piping were energized at 120 volts. He crawled under the trailer to look for faulty wiring. As he was crawling under the trailer, he passed over a copper refrigerant line that was also energized. The employee was electrocuted. An inspection of the main panelboard discovered that the main bonding jumper was missing.

Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, MOBILE HOME, LOCKOUT, GROUND FAULT, EQUIPMENT GROUNDING, SYSTEM GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 112038500 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.