Inspection Detail
Inspection: 112038500 - Don Hegge Electric
Inspection Information - Office: San Bernardino District Office
Site Address:
Don Hegge Electric
73060 Broadmoor Dr.
Thousand Palms, CA 92276
Mailing Address:
4639 Sunny Dunes, Palm Springs, CA 92262
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 12/04/1990
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 12/19/1990
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 361306475 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 23950050 A | 12/20/1990 | 12/04/1990 | $0 | $0 | $0 | - |
Investigation Summary
An electrical contractor had been hired by a mobile home owner to determine why the owner was receiving electric shocks from the outside piping. An electrician with about 4 years of experience was assigned the job. The employee determined that the trailer frame and the piping were energized at 120 volts. He crawled under the trailer to look for faulty wiring. As he was crawling under the trailer, he passed over a copper refrigerant line that was also energized. The employee was electrocuted. An inspection of the main panelboard discovered that the main bonding jumper was missing.
Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, MOBILE HOME, LOCKOUT, GROUND FAULT, EQUIPMENT GROUNDING, SYSTEM GROUNDING
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 112038500 | Fatality | Electric Shock | Electricians |