Inspection Detail
Inspection: 112014147 - California State Of Patton Hospital
Inspection Information - Office: San Bernardino District Office
Site Address:
California State Of Patton Hospital
3102 East Highland Avenue
Patton, CA 92369
Mailing Address:
, , 00000
Union Status: Union
SIC:8999
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 09/05/1991
Emphasis:
Case Closed: 09/26/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361331754 |
Investigation Summary
AN ELECTRICIAN WAS TRYING TO IDENTIFY A CIRCUIT. HE WAS GOING TO INSTALL A JUMPER WIRE BETWEEN TWO PHASE CONDUCTORS OF THE CIRCUIT TO PERFORM THIS TASK. THE TWO CONDUCTORS WERE LOCATED SOME DISTANCE FROM THE SWITCHGEAR, BUT THE ELECTRICIAN HAD ASSUMED THAT HE HAD DEENERGIZED THE CONDUCTORS. HOWEVER, A CONTRACTOR HAD PREVIOUSLY REVERSED THE PRIMARY AND SECONDARY LEADS (PRESUMABLY OF A TRANSFORMER), AND THE FUSE CLIPS AND ALL CONNECTED CONDUCTORS FOR THIS CIRCUIT REMAINED ENERGIZED EVEN WHEN THE CIRCUIT WAS "OPENED". WHEN THE ELECTRICIAN INSTALLED THE JUMPER, IT CREATED A FAULT IN THE ENERGIZED CIRCUIT. THE JUMPER WIRE EXPLODED, RESULTING IN FLASH BURNS TO THE EMPLOYEE, WHO WAS HOSPITALIZED FOR HIS INJURIES.
Keywords: BURN, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 112014147 | Hospitalized injury | Burn/Scald(Heat) | Electricians |