Inspection Detail
Inspection: 112004866 - San Diego Gas & Electric
Inspection Information - Office: San Diego District Office
Site Address:
San Diego Gas & Electric
4500 Otay Mesa Rd
San Diego, CA 92173
Mailing Address:
114 10th Ave, San Diego, CA 92101
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/28/1992
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 09/11/1992
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361366842 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 1 | 3 | |||
| Current Violations | 2 | 1 | 3 | |||
| Initial Penalty | $1,050 | $0 | $0 | $2,000 | $0 | $3,050 |
| Current Penalty | $1,050 | $0 | $0 | $2,000 | $0 | $3,050 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 2944 G | 09/03/1992 | 09/03/1992 | $700 | $700 | $0 | - | ||
| 2. | 02001 | Serious | 2944 H02 E | 09/03/1992 | 09/03/1992 | $350 | $350 | $0 | - | ||
| 3. | 03001 | Other | 2944 H01 C | 08/28/1992 | 08/28/1992 | $2,000 | $2,000 | $0 | - |
Investigation Summary
A crew of electricians for an electric utility was performing routine maintenance in a substation. A journeyman electrician and an apprentice were assigned to service 12-kilovolt bus disconnects. The disconnects were not originally scheduled in this job; however, since they were available for servicing, the foreman decided to do them as well. One end of the line (#102) to the disconnects had already been deenergized, locked out, and tagged. the electrician was instructed to deenergize the other end of the line (#101). The electrician was then supposed to service the deenergized contacts at both ends before reenergizing disconnect #101. However, the electrician reenergized disconnect #101 before he serviced disconnect #102. He received an electric shock when his oil squirt can contacted the energized conductor at disconnect #102. He was hospitalized for his injuries.
Keywords: ELECTRICAL, ELECTRIC SWITCH, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, E PTD, SUBSTATION, ELECTRIC SHOCK, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 112004866 | Hospitalized injury | Electric Shock | Misc. electrical & electronic equipment repairers |
Translate