Powered by GoogleTranslate

Inspection Detail

Inspection: 111992509 - R J Locicero

Inspection Information - Office: American Canyon District Office

 

Inspection Nr: 111992509
Report ID: 0950615
Date Opened: 11/22/1991

Site Address:
R J Locicero
138 Rowland Blvd.
Novato, CA 94954

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:1761

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/25/1991

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 11/25/1991


Related Activity
Type Activity Nr Safety Health
Accident 361321847
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 3 4
Current Violations 1 3 4
Initial Penalty $225 $0 $0 $0 $0 $225
Current Penalty $225 $0 $0 $0 $0 $225
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 25100004 11/25/1991 11/22/1991 $0 $0 $0 -  
2. 01002 Other 24050004 C 11/25/1991 11/22/1991 $0 $0 $0 -  
3. 01003 Other 342 A 11/25/1991 11/22/1991 $0 $0 $0 -  
4. 02001 Serious 1670 A 11/25/1991 11/25/1991 $225 $225 $0 -  

Investigation Summary

Investigation Nr: 170206916
Event: 11/22/1991
ELECTRIC SHOCK - GROUND FAULT IN ATTACHMENT PLUG

AN EMPLOYEE WAS SETTING UP TO INSTALL STEEL STUDS ON A TOWER THAT HAD BEEN BUILT ON THE ROOF OF A BUILDING. HE HAD PLUGGED A TWO-POLE ATTACHMENT PLUG FOR A RADIO INTO A TWIST-LOCK CONNECTOR BUT HAD LEFT PART OF THE PLUG'S BLADES EXPOSED. THE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTING THE CORD SET HAD BEEN WIRED OUT OF THE CIRCUIT AT THE TEMPORARY POWER SUPPLY BOX BY AN UNKNOWN PERSON. THE EMPLOYEE WAS USING AN ELECTRIC SCREW GUN TO INSTALL A STEEL STUD BASE CHANNEL. THE SCREW GUN WAS PLUGGED INTO THE SAME CORD AS THE RADIO. AS HE WAS WORKING, THE CORD MOVED, AND THE EXPOSED PART OF THE BLADE FOR THE UNGROUNDED CIRCUIT CONDUCTOR FOR THE RADIO CONTACTED THE BASE CHANNEL, ENERGIZING IT. WHEN THE EMPLOYEE, STANDING ON THE WET ROOF AND GROUNDED THROUGH THE EQUIPMENT GROUNDING CONDUCTOR ON THE SCREW GUN, BEGAN TO INSERT THE NEXT SCREW, HE RECEIVED AN ELECTRIC SHOCK AND WAS KNOCKED UNCONSCIOUS. THE EMPLOYEE WAS HOSPITALIZED FOR AN IRREGULAR HEARTBEAT.

Keywords: E GI V, METAL RAIL, ELECTRICAL, ATTACHMENT PLUG, GROUND FAULT, CORD CONNECTOR, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 111992509 Hospitalized injury Electric Shock Structural metal workers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.