Powered by GoogleTranslate

Inspection Detail

Inspection: 111970232 - Burnup & Sims Of Calif., Inc.

Inspection Information - Office: Redding District Office

 

Inspection Nr: 111970232
Report ID: 0950623
Date Opened: 12/18/1991

Site Address:
Burnup & Sims Of Calif., Inc.
Intanco Lane
Wheatland, CA 95692

Mailing Address:
650 N. Winchester Blvd., Sutie 6, San Jose, CA 95128

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/16/1992

Emphasis:

Case Closed: 02/09/1994


Related Activity
Type Activity Nr Safety Health
Accident 361356496
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 3 5
Current Violations 2 3 5
Initial Penalty $2,500 $0 $0 $0 $0 $2,500
Current Penalty $625 $0 $0 $0 $0 $625
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 C 02/20/1992 03/02/1992 $0 $0 $0 03/18/1992 J - ALJ Decision  
2. 01002 Other 1509 A 02/20/1992 03/25/1992 $0 $0 $0 03/18/1992 J - ALJ Decision  
3. 01003 Other 8603 A03 02/20/1992 03/25/1992 $0 $0 $0 03/18/1992 J - ALJ Decision  
4. 02001 Serious 8615 J02 02/20/1992 12/20/1991 $500 $2,000 $0 03/18/1992 J - ALJ Decision  
5. 03001 Serious 8615 A01 02/20/1992 12/20/1991 $125 $500 $0 03/18/1992 J - ALJ Decision  

Investigation Summary

Investigation Nr: 170697015
Event: 12/03/1991
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU STEEL RULE

AN EMPLOYEE WAS SUPERVISING THE INSTALLATION OF A NEW TELEPHONE LINE. HE WAS WORKING FROM AN AERIAL LIFT AND HAD JUST DRILLED A HOLE THROUGH A UTILITY POLE FOR AN ATTACHMENT TO HOLD THE TELEPHONE SUSPENSION STRAND. HE DECIDED TO RECHECK HIS CLEARANCE FROM THE 12-KILOVOLT OVERHEAD POWER LINE ABOVE HIM. HE SLID HIS STEEL POCKET TAPE UP ALONGSIDE THE POLE; AND, WHEN THE MEASURING TAPE WAS EXTENDED NEAR THE POWER LINE, IT FELL OR WAS BLOWN OVER INTO A JUMPER FROM A CUTOUT TO THE 7200-VOLTS-TO-GROUND POWER LINE CONDUCTOR. THE SUPERVISOR RECEIVED AN ELECTRIC SHOCK. HE REMAINED CONSCIOUS, BUT HIS CREW HAD TO LOWER HIM TO THE GROUND USING THE LOWER CONTROLS ON THE AERIAL LIFT. THE EMPLOYEE WAS HOSPITALIZED FOR BURNS TO THE BONE IN HIS RIGHT HAND, TO HIS LEFT SIDE (THIS BURN WAS 8 INCHES IN DIAMETER), TO THE MIDDLE FINGER ON HIS LEFT HAND, AND TO HIS RIGHT LEG.

Keywords: BURN, OVERHEAD POWER LINE, ELECTRICAL, TELECOM WORK, MEASURING DEVICE, E TC, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 111970232 Hospitalized injury Electric Shock Supervisors, mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close