Inspection Detail
Inspection: 111898268 - Shasta-Trinity Rural Indian Health Clinic
Inspection Information - Office: Redding District Office
Site Address:
Shasta-Trinity Rural Indian Health Clinic
2110 North Street
Anderson, CA 96007
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:8011
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/19/1990
Emphasis:
Case Closed: 12/04/1990
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361049000 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 3273 A | 07/19/1990 | 08/30/1990 | $0 | $0 | $0 | - | ||
| 2. | 01002 | Other | 23400026 A | 07/19/1990 | 08/30/1990 | $0 | $0 | $0 | - |
Investigation Summary
A dentist entered a dental lab area and discovered that the circuit supplying an ultrasonic cleaning machine was deenergized. She opened cover to the panelboard supplying branch circuits for the area and noticed that one of the circuit breakers was tripped. She was standing with her right foot just to the side of a floor receptacle. When she reset the circuit breaker, an electrical fault occurred in the receptacle outlet. The ensuing electric arc burned the back of her right leg. The employer had not installed covers for the floor receptacles that had been exposed during remodeling.
Keywords: BURN, E GI V, ELECTRIC ARC, RECEPTACLE, ELECTRICAL, ELECTRICAL FAULT, OVERCURRENT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 111898268 | Non Hospitalized injury | Burn/Scald(Heat) | Dentists |