Inspection Detail
Inspection: 111853602 - R. C. Collett Asphalt, Inc.
Inspection Information - Office: Sacramento District Office
Site Address:
R. C. Collett Asphalt, Inc.
900 W. Elkhorn Blvd.
Rio Linda, CA 95673
Mailing Address:
P.O. Box 1965, Woodland, CA 95695
Union Status: Union
SIC:2951
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/16/1991
Emphasis:
Case Closed: 05/29/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361284482 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | 2 | |||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $150 | $0 | $0 | $0 | $0 | $150 |
| Current Penalty | $150 | $0 | $0 | $0 | $0 | $150 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 3329 B | 05/16/1991 | 05/06/1991 | $0 | $0 | $0 | - | ||
| 2. | 02001 | Serious | 4070 A | 05/16/1991 | 05/24/1991 | $150 | $150 | $0 | - |
Investigation Summary
On April 23, 1991, Employee #1, of R. C. Collett Asphalt, was on duty when the type of asphalt mix was being changed. This required the oil be drained from the system back into the heated storage tank. The valves on the alternate tank were then opened and the return pipe valve was double-checked. The pumping system to the mixer had one pump to send the oil from the tank and another to meter the oil to the mixer. Between the two pumps was a return-bypass pipeline with a surge tank mounted near the first pump. The pump system had no pressure relief valve. When the pumping began, the return pipe valve at the tank was not preventing the surplus oil from returning to the storage tank. This resulted in pressure building up in the return pipeline and surge tank, which was not designed as a pressure tank. After several minutes, the pressure in the surge tank exceeded its capacity and the tank burst, spraying hot oil over Employee #1. He suffered first- and second-degree burns on his face and chest. He would have sustained more severe burns if the oil in the surge tank had not cooled to below 200 degrees F.
Keywords: BURN, CHEST, SAFETY RELIEF VALVE, WORK RULES, STORAGE TANK, HIGH PRESSURE, FACE, PRESSURE RELEASE, HIGH TEMPERATURE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 111853602 | Hospitalized injury | Burn/Scald(Heat) | Miscellaneous plant and system operators |