Inspection Detail
Inspection: 111850376 - Pacific Mechanical Corporation
Inspection Information - Office: American Canyon District Office
Site Address:
Pacific Mechanical Corporation
1761 Atlas Peak Road
Napa, CA 94558
Mailing Address:
P.O. Box 4041, Concord, CA 94524
Union Status: NonUnion
SIC:1542
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/07/1990
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 04/26/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361302631 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | 2 | |||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 342 A | 11/07/1990 | 10/15/1990 | $0 | $0 | $0 | 11/29/1990 | J - ALJ Decision | |
| 2. | 02001 | Serious | 560 A02 | 11/07/1990 | 10/13/1990 | $2,000 | $2,000 | $0 | 11/29/1990 | J - ALJ Decision |
Investigation Summary
At approximately 11:45 p.m. on October 13, 1990, Employee #1, a mechanical supervisor, was working on a well water supply system for a winery. His employer had been engaged to install the equipment. Water was spraying from a pressure relief valve on the well line, but no water was available from the tank. Employee #1 was asked to supply water to the winery from one of two newly installed 100,000 gallon storage tanks on site. Employee #1 began work on a 220 gallon tank, not the larger tanks as had been requested. During the effort to direct water from the functional deep water well, Employee #1 attempted to force water into the 220 gallon galvanized cold water pressure tank by placing a threaded 1/2 in. plug into the vent hole. The tank exploded, killing Employee #1.
Keywords: AIR PRESSURE, WORK RULES, CONSTRUCTION, STORAGE TANK, EXPLOSION, HIGH PRESSURE, PRESSURE RELEASE, WATER
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 111850376 | Fatality | Other | Plumbers, pipefitters and steamfitters |
Translate