Inspection Detail
Inspection: 111805560 - P G & E
Inspection Information - Office: Foster City District Office
Site Address:
P G & E
Oyster Point Blvd At Eccles Ave.
South San Francisco, CA 94080
Mailing Address:
Mail Code H4a, P.O.Box 770000, San Francisco, CA 94177
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/27/1997
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 03/04/1998
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 362304305 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
Current Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 29400002 A | 01/24/1997 | 11/08/1996 | $5,000 | $5,000 | $0 | 02/13/1997 | F - Formal Settlement |
Investigation Summary
A power line crew had just finished alterations to an overhead power line. The crew was working on a deenergized line that was located above an energized line on the supporting utility poles. One of the power line workers on the crew was instructed to climb a utility pole and close the open cutouts with a 2.4-meter-long hot stick. The hot stick was not long enough to reach the top-most cutout, so the employee climbed higher, between the conductors on the energized line. As he was descending the pole, the employee's shoulder touched one of the energized conductors. He received an electric shock and sustained severe burns. He was hospitalized for a month for treatment of his injuries.
Keywords: BURN, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 111805560 | Hospitalized injury | Electric Shock | Electrical power installers and repairers |