Inspection Detail
Inspection: 111698312 - Arrowhead Electric Coop, Inc.
Inspection Information - Office: Minnesota Department Of Labor And Industry
Site Address:
Arrowhead Electric Coop, Inc.
Ja -05 Gunflint Trail
Grand Marais, MN 55604
Mailing Address:
Po Box 38, Lutsen, MN 55612
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/09/1990
Emphasis:
Case Closed: 02/04/1993
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360239669 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 3 | 3 | ||||
| Initial Penalty | $30,000 | $0 | $0 | $0 | $0 | $30,000 |
| Current Penalty | $10,000 | $0 | $0 | $0 | $0 | $10,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 182065302 | 12/20/1990 | 12/01/1991 | $3,333 | $10,000 | $0 | 01/15/1991 | R - Review Commission | |
| 2. | 01002 | Serious | 19260021 B 2 | 12/20/1990 | 12/01/1991 | $3,333 | $10,000 | $0 | R - Review Commission | ||
| 3. | 01003 | Serious | 19260020 B 1 | 12/20/1990 | 12/01/1991 | $3,334 | $10,000 | $0 | R - Review Commission |
Investigation Summary
Two power line workers were installing a guy on a utility pole. Both employees were standing on the ground. One of them was using a hoist to apply tension to the guy before it was attached to its ground anchor. The other employee was handling coils of wire at the free end of the guy spool, to keep the free wire out of the first employee's way. A jumper wire for connecting the guy to the neutral conductor had been clamped to the top end of the guy. The jumper had not yet been connected to the neutral, however. As the hoist applied tension to the guy, the wire rotated, moving the free end of the jumper into contact with an overhead power line on the pole. The employees, who were both in contact with the guy at the time, were electrocuted.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, GUY, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 111698312 | Fatality | Electric Shock | Electrical power installers and repairers | ||
| 2 | 111698312 | Fatality | Electric Shock | Electrical power installers and repairers |