Powered by GoogleTranslate

Inspection Detail

Inspection: 111623286 - Premier Electric

Inspection Information - Office: Minnesota Department Of Labor And Industry

 

Inspection Nr: 111623286
Report ID: 0552700
Date Opened: 10/11/1990

Site Address:
Premier Electric
3400 48th Avenue North
Minneapolis, MN 55429

Mailing Address:
, , 00000

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/29/1990

Emphasis:

Case Closed: 12/27/1994


Related Activity
Type Activity Nr Safety Health
Accident 360239685
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 1 2 3
Initial Penalty $8,256 $0 $0 $0 $0 $8,256
Current Penalty $2,000 $0 $0 $0 $0 $2,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 12/07/1990 12/10/1990 $2,000 $8,256 $0 12/17/1990 F - Formal Settlement  
2. 02001 Other 19260025 A 12/07/1990 12/10/1990 $0 $0 $0 -  
3. 02002 Other 19260450 A 1 12/07/1990 12/10/1990 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 814020
Event: 10/11/1990
ELECTRIC SHOCK - CONTACT WITH LIVE PARTS THRU METAL TAPE

TWO ELECTRICIANS AND A RADIO LIAISON WERE INSTALLING A RUNWAY DISTANCE MARKER SIGN. ONE OF THE ELECTRICIANS WAS CONNECTING THE TRANSFORMER LEADS FOR THE SIGN TO THE RUNWAY CIRCUIT WIRING. THE RUNWAY CIRCUIT WAS STILL ENERGIZED AT THE TIME. AS THE EMPLOYEE PULLED APART THE CABLE, HE CONTACTED AN 1800-VOLT CONDUCTOR AND WAS ELECTROCUTED. THE OTHER ELECTRICIAN, WHO WAS RIGHT BEHIND THE FIRST ELECTRICIAN, HEARD AN ARC AND BUMPED INTO HIS COWORKER, KNOCKING BOTH OF THEM DOWN. (THE RADIO LIAISON CALLED THE RADIO TOWER FOR HELP.) THE SECOND ELECTRICIAN RECEIVED A SEVERE ELECTRIC SHOCK, FOR WHICH HE WAS HOSPITALIZED.

Keywords: METAL WIRE, E GI IV, ELECTRICAL, ELECTRIC CONDUCTOR, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 111623286 Fatality Electric Shock Supervisors; electricians & power transm. install.
2 111623286 Hospitalized injury Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close