Powered by GoogleTranslate

Inspection Detail

Inspection: 111350591 - Seattle City Light

Inspection Information - Office: Dosh Spokane Service Location, Spokane, Wa

 

Inspection Nr: 111350591
Report ID: 1055360
Date Opened: 10/01/1991

Site Address:
Seattle City Light
2nd & Union St
Seattle, WA 98104

Mailing Address:
1015 Third Ave, Seattle, WA 98104

Union Status: Union

SIC:9131

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 10/08/1991

Emphasis: L:Euc

Case Closed: 07/20/1992


Related Activity
Type Activity Nr Safety Health
Accident 361193543
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $7,680 $0 $0 $0 $0 $7,680
Current Penalty $7,680 $0 $0 $0 $0 $7,680
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 0456503703IV 11/07/1991 10/08/1991 $1,400 $1,400 $0 11/27/1991 Y - State Decision  
2. 01002 Serious 0621450303 11/07/1991 01/08/1992 $680 $680 $0 11/27/1991 Y - State Decision  
3. 01003 Serious 0621450301 11/07/1991 01/08/1992 $1,600 $1,600 $0 11/27/1991 Y - State Decision  
4. 01004 Serious 0621450302 11/07/1991 01/08/1992 $3,200 $3,200 $0 11/27/1991 Y - State Decision  
5. 01005A Serious 0240004001 A 03 11/07/1991 04/06/1992 $800 $800 $0 11/27/1991 Y - State Decision  
6. 01005B Serious 0240004001 A 05 11/07/1991 01/08/1992 $0 $0 $0 11/27/1991 Y - State Decision  
7. 01005C Serious 0240004001 A 07 11/07/1991 01/08/1992 $0 $0 $0 11/27/1991 Y - State Decision  

Investigation Summary

Investigation Nr: 170000293
Event: 09/30/1991
BURN - EXPLOSION IN MANHOLE DUE TO NATURAL GAS LEAK

Two city workers were assigned to replace a streetlight fuse in an underground manhole. When the employees arrived at the worksite, they monitored the manhole's air quality for about 5 minutes before one of them entered. His coworker stood above the manhole opening while he replaced the fuse on a streetlight contactor. When the employee closed the contactor, an explosion occurred. A natural gas leak had created a flammable atmosphere inside the manhole. Both employees received second-degree burns and were hospitalized for their injuries.

Keywords: BURN, FUSE, LEAK, ELECTRICAL, POWER LINE WORKER, NATURAL GAS, E PTD, ELEC UTILITY WORK, MANHOLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 111350591 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
2 111350591 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.