Inspection Detail
Inspection: 111345120 - Puget Power Co
Inspection Information - Office: Dosh Spokane Service Location, Spokane, Wa
Site Address:
Puget Power Co
Se 208th & 124th Ave Se
Kent, WA 98042
Mailing Address:
Puget Power Bldg, Bellevue, WA 98009
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/09/1992
Emphasis: L:Euc
Case Closed: 03/02/1993
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $1,500 | $0 | $0 | $0 | $0 | $1,500 |
| Current Penalty | $1,500 | $0 | $0 | $0 | $0 | $1,500 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 0456502707 | 01/26/1993 | 10/09/1992 | $1,500 | $1,500 | $0 | - |
Investigation Summary
TWO POWER LINE WORKERS WERE CONNECTING JUMPERS ON PINS AND INSULATORS ON DOUBLE DEAD-END CROSSARMS. THEY WERE WORKING FROM AN AERIAL LIFT. THE CONDUCTORS ON THE EAST SIDE OF THE CROSSARMS WERE NEW AND HAD NEVER BEEN ENERGIZED. HOWEVER, THE EMPLOYEES HAD NOT INSTALLED ANY INSULATING EQUIPMENT TO PROTECT AGAINST CONTACT WITH THE EXISTING 12.5-KILOVOLT OVERHEAD POWER LINE ON THE POLE. TO CONNECT A JUMPER, ONE OF THE EMPLOYEES UNCOILED AN ALUMINUM TIE WIRE AND CONTACTED AN ENERGIZED CONDUCTOR LOCATED ABOUT 44 INCHES AWAY. BOTH EMPLOYEES APPARENTLY RECEIVED ELECTRIC SHOCKS.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 111345120 | Non Hospitalized injury | Electric Shock | Electrical power installers and repairers | ||
| 2 | 111345120 | Non Hospitalized injury | Electric Shock | Electrical power installers and repairers |
Translate