Powered by GoogleTranslate

Inspection Detail

Inspection: 111137741 - Frank Edward Davis Dba Frank'S Roofing Co.

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 111137741
Report ID: 0453710
Date Opened: 07/15/1992

Site Address:
Frank Edward Davis Dba Frank'S Roofing Co.
Highway 501 S.
Roxboro, NC 27573

Mailing Address:
6204 Guess Rd., Rougemont, NC 27572

Union Status: NonUnion

SIC:1761

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/03/1992

Emphasis:

Case Closed: 06/28/1993


Related Activity
Type Activity Nr Safety Health
Accident 360490874
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6
Current Violations 6 6
Initial Penalty $16,800 $0 $0 $0 $0 $16,800
Current Penalty $1,680 $0 $0 $0 $0 $1,680
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 09/21/1992 09/28/1992 $280 $2,800 $0 10/08/1992 J - ALJ Decision  
2. 01002 Serious 19260404 B01 I 09/21/1992 09/28/1992 $280 $2,800 $0 10/08/1992 J - ALJ Decision  
3. 01003 Serious 19260404 F06 09/21/1992 09/28/1992 $280 $2,800 $0 10/08/1992 J - ALJ Decision  
4. 01004 Serious 19260405 G02 III 09/21/1992 09/28/1992 $280 $2,800 $0 10/08/1992 J - ALJ Decision  
5. 01005 Serious 19260405 G02 IV 09/21/1992 09/28/1992 $280 $2,800 $0 10/08/1992 J - ALJ Decision  
6. 01006 Serious 19260416 E01 09/21/1992 09/28/1992 $280 $2,800 $0 10/08/1992 J - ALJ Decision  

Investigation Summary

Investigation Nr: 170063846
Event: 07/14/1992
ELECTRIC SHOCK - GROUND FAULT IN CORD SET

A ROOFER WAS USING A MILWAUKEE ELECTRIC DRILL. THE DRILL WAS PLUGGED INTO TWO 100-FOOT EXTENSION CORD SETS, BOTH OF WHICH HAD THE GROUNDING BLADES ON THEIR ATTACHMENT PLUGS REMOVED. (THE GROUNDING BLADE ON THE PLUG ON THE DRILL'S POWER SUPPLY CORD WAS INTACT.) THE CORD SET THAT WAS CONNECTED TO THE DRILL HAD BEEN IMPROPERLY SPLICED. INSULATION ON BOTH THE EQUIPMENT GROUNDING CONDUCTOR AND THE UNGROUNDED CIRCUIT CONDUCTOR HAD BEEN REMOVED, EXPOSING THE BARE COPPER CONDUCTORS. THE CONDUCTORS WERE THEN BUNDLED AND WRAPPED WITH DUCT TAPE. (THEY WERE NOT INDIVIDUALLY WRAPPED.) UPON INSPECTION, THE UNGROUNDED CIRCUIT CONDUCTOR AND THE EQUIPMENT GROUNDING CONDUCTOR WERE FOUND TO HAVE MADE CONTACT. THIS IMPOSED THE FULL CIRCUIT VOLTAGE ON THE DRILL'S METAL HOUSING. THE CIRCUIT TO WHICH THE DRILL WAS CONNECTED WAS NOT PROTECTED BY A GROUND-FAULT CIRCUIT INTERRUPTER. THE EMPLOYEE, WHO WAS PERSPIRING BECAUSE OF THE HEAT AND HUMIDITY, WAS ELECTROCUTED AS HE HELD THE DRILL IN BOTH HANDS.

Keywords: ELEC INSULATION, ELECTRICAL, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, E GI V, CORD SET, ELECTROCUTED, ELECTRICAL SPLICE, ELECTRIC DRILL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 111137741 Fatality Electric Shock Construction laborers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.