Powered by GoogleTranslate

Inspection Detail

Inspection: 111135133 - Marshall Contractors, Inc.

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 111135133
Report ID: 0453710
Date Opened: 03/06/1992

Site Address:
Marshall Contractors, Inc.
3039 Cornwallis Drive
Research Triangle Park, NC 27709

Mailing Address:
3001-A Weston Parkway, Cary, NC 27513

Union Status: NonUnion

SIC:1541

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/06/1992

Emphasis:

Case Closed: 11/10/1993


Related Activity
Type Activity Nr Safety Health
Accident 360490221
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $6,300 $0 $0 $0 $0 $6,300
Current Penalty $6,300 $0 $0 $0 $0 $6,300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A03 08/17/1992 08/24/1992 $6,300 $6,300 $0 08/31/1992 F - Formal Settlement  

Investigation Summary

Investigation Nr: 170063499
Event: 03/05/1992
ELECTRIC SHOCK - CONTACT WITH UND'GROUND LINE THRU METAL ROD

A FOUR-MAN CREW WAS INSTALLING A SUBSTATION IN AN EMPTY ROOM IN A COMPUTER MANUFACTURER'S BUILDING. THE CONSTRUCTION PLANS CALLED FOR EIGHT 10-FOOT-LONG, 0.625-INCH-DIAMETER COPPER RODS TO BE DRIVEN INTO THE GROUND UNDER THE CONCRETE FLOOR WITHIN THE ROOM. EIGHT HOLES HAD BEEN CUT INTO THE FLOOR TO EXPOSE THE EARTH. THE CREW THEN USED A PNEUMATIC HAMMER TO DRIVE THE FIRST ROD INTO ITS HOLE, WHICH WAS ABOUT MIDWAY ALONG THE SOUTH WALL OF THE ROOM. THE SUPERVISOR (EMPLOYEE #1) AND ANOTHER WORKER (EMPLOYEE #3) OPERATED THE HAMMER, WHILE THE OTHER TWO EMPLOYEES SUPPORTED THE ROD. WHEN THE ROD REACHED A DEPTH OF ABOUT 6.5 FEET, IT PENETRATED A 13.2-KILOVOLT UNDERGROUND POWER LINE. ALL FOUR EMPLOYEES WERE HOSPITALIZED FOR THE ELECTRIC SHOCKS THEY RECEIVED.

Keywords: METAL WIRE, ELECTRICAL, ELECTRIC SHOCK, UNDRGRD POWER LINE, E PTD, SUBSTATION, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 111135133 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.