Powered by GoogleTranslate

Inspection Detail

Inspection: 110362233 - Maguire Thomas Partners

Inspection Information - Office: Fort Worth Area Office

 

Inspection Nr: 110362233
Report ID: 0636900
Date Opened: 02/25/1992

Site Address:
Maguire Thomas Partners
9 Village Circle, Ste. 200
Westlake, TX 76262

Mailing Address:
9 Village Circle, Ste 500, Roanoke, TX 76262

Union Status: NonUnion

SIC:6512

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/09/1992

Emphasis:

Case Closed: 06/10/1992


Related Activity
Type Activity Nr Safety Health
Referral 901562900 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $3,500 $0 $0 $0 $0 $3,500
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100333 A 04/22/1992 05/04/1992 $0 $3,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 566109
Event: 02/25/1992
BURN - ELECTRICAL FAULT IN ELECTRICAL BOX

A MAINTENANCE CREW OF THREE ELECTRICIANS WAS REPLACING A 480-VOLT, 400-AMPERE MAIN DISCONNECT BOX IN AN ELECTRICAL CONTROL ROOM. THE ELECTRIC POWER FOR THE DISCONNECT WAS RESTORED AFTER THE BOX WAS PLUGGED INTO THE BUS DUCT RISER. TWO OF THE ELECTRICIANS WERE ATTACHING THE CONDUCTORS TO THE LUGS INSIDE THE BOX. A BOLT ON ONE OF THE LUGS SHEARED OFF, AND A PIECE OF THE BOLT DROPPED TO THE BOTTOM OF THE DISCONNECT BOX. ONE OF THEM TRIED TO RETRIEVE THE PIECE AND CONTACTED AN ENERGIZED PART WITHIN THE ENCLOSURE. THIS CAUSED AN ELECTRICAL FAULT, AND THE ENSUING ELECTRIC ARC BURNED THE EMPLOYEE ON HIS FACE AND RIGHT ARM. HE WAS HOSPITALIZED FOR HIS INJURIES. THE SECOND ELECTRICIAN SUSTAINED BURNS OVER MOST OF HIS FACE.

Keywords: ELECTRIC ARC, ELECTRICAL, BURN, CLOTHING, ELECTRICIAN, LOCKOUT, ELECTRICAL BOX, E GI IV, ELECTRICAL FAULT, ELECTRICAL WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 110362233 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.