Powered by GoogleTranslate

Inspection Detail

Inspection: 110130960 - Seminole Kraft Corporation

Inspection Information - Office: Jacksonville Area Office

 

Inspection Nr: 110130960
Report ID: 0419700
Date Opened: 12/10/1993

Site Address:
Seminole Kraft Corporation
9469 Eastport Road
Jacksonville, FL 32218

Mailing Address:
P.O. Box 26998, Jacksonville, FL 32226

Union Status: Union

SIC:2621

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/10/1993

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 06/08/1995


Related Activity
Type Activity Nr Safety Health
Referral 901951194 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 3 3
Initial Penalty $13,125 $0 $0 $0 $0 $13,125
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100022 A01 05/18/1994 05/24/1994 $3,500 $5,250 $0 06/10/1994 R - Review Commission  
2. 01002A Serious 19100036 B04 05/18/1994 06/14/1994 $0 $1,500 $0 06/10/1994 R - Review Commission Citation has been deleted.
3. 01002B Serious 19100037 K02 05/18/1994 05/24/1994 $750 $0 $0 06/10/1994 R - Review Commission  
4. 01003 Serious 19100037 Q01 05/18/1994 06/07/1994 $750 $1,125 $0 06/10/1994 R - Review Commission  
5. 01004A Serious 19100333 A01 05/18/1994 06/14/1994 $0 $5,250 $0 06/10/1994 R - Review Commission Citation has been deleted.
6. 01004B Serious 19100333 A 05/18/1994 06/14/1994 $0 $0 $0 06/10/1994 R - Review Commission Citation has been deleted.

Investigation Summary

Investigation Nr: 14338024
Event: 12/09/1993
BURN - ELECTRICAL FAULT IN SUBSTATION CABINET

A four-person crew was installing circuit breakers in two cubicles in a substation. The electric power to the busbars in the cubicles was not deenergized. Some of the busbars were covered with rubber insulating blankets; however, some energized parts were still exposed. Conductive material contacted an exposed energized busbar, resulting in an electrical fault. The ensuing electric arc burned two employees; one of them (the one covered by this abstract) died of his injuries.

Keywords: ELECTRIC ARC, ELECTRICAL, BURN, CLOTHING, LOCKOUT, BUSBAR, ELECTRICAL CABINET, ELECTRICAL FAULT, ELEC PROTECT EQUIP, E PTD

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 110130960 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.