Inspection Detail
Inspection: 110103884 - Fluor Enterprises, Inc.
Inspection Information - Office: Atlanta East Area Office
Site Address:
Fluor Enterprises, Inc.
Hwy 56 South, P.O. Box 9389
Augusta, GA 30906
Mailing Address:
100 Fluor Daniel Drive, Greenville, SC 29607
Union Status: NonUnion
SIC:1541
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/21/1990
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 11/30/1990
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360414874 |
Investigation Summary
TWO EMPLOYEES WERE REMOVING A CONDUIT FROM A BEAM THAT WAS TO BE TAKEN OUT. TWO OVERHEAD LIGHTING FIXTURES WERE SUPPLIED BY THIS CONDUIT, AND THE EMPLOYEES WERE INSTALLING A NON-METALLIC SHEATHED CABLE BETWEEN TWO JUNCTION BOXES TO REPLACE IT. ONE OF THE TWO EMPLOYEES DECIDED TO WIRE ONE OF THE JUNCTION BOXES WHILE IT REMAINED ENERGIZED AT 480/277 VOLTS (THREE PHASE, FOUR WIRE). THE EMPLOYEE SUCCESSFULLY CONNECTED THE BLACK CONDUCTOR, INSTALLING A WIRE NUT AND TAPING THE CONNECTION. HE HAD CONTACTED AN ENERGIZED PART AND HAD RECEIVED AN ELECTRIC SHOCK. HOWEVER, HE CONTINUED TO WORK WITH THE CIRCUIT ENERGIZED. HE THEN APPARENTLY BEGAN TO STRIP THE INSULATION FROM THE RED CONDUCTOR. HE RECEIVED A SECOND ELECTRIC SHOCK AND WAS ELECTROCUTED. HIS EMPLOYER HAD A LOCKOUT AND TAGGING PROGRAM AND AN ELECTRICAL HOT WORK PERMIT SYSTEM IN PLACE. THE PROGRAMS WERE EFFECTIVELY COMMUNICATED TO EMPLOYEES AND WERE UNIFORMLY ENFORCED.
Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL BOX
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 110103884 | Fatality | Electric Shock | Electricians |