Powered by GoogleTranslate

Inspection Detail

Inspection: 109944702 - Ferguson Electric Construction Co., Inc.

Inspection Information - Office: Buffalo Area Office

 

Inspection Nr: 109944702
Report ID: 0213600
Date Opened: 12/07/1999

Site Address:
Ferguson Electric Construction Co., Inc.
Itt Heat Transfer, 175 Standard Parkway
Cheektowaga, NY 14227

Mailing Address:
321 Ellicott Street, Buffalo, NY 14203

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Referral

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/05/2000

Emphasis: S:Construction

Case Closed: 10/19/2000


Related Activity
Type Activity Nr Safety Health
Accident 361817661
Referral 902629534 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 3 3
Initial Penalty $20,000 $0 $0 $0 $0 $20,000
Current Penalty $12,000 $0 $0 $0 $0 $12,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100269 A02 06/06/2000 06/10/2000 $4,000 $5,000 $0 06/29/2000 J - ALJ Decision  
2. 01001B Serious 19100269 O02 II 06/06/2000 06/10/2000 $0 $0 $0 06/29/2000 J - ALJ Decision  
3. 01002 Serious 19100269 C 06/06/2000 06/10/2000 $4,000 $5,000 $0 06/29/2000 J - ALJ Decision  
4. 01003A Serious 19100269 M03 V 06/06/2000 06/10/2000 $4,000 $5,000 $0 06/29/2000 J - ALJ Decision  
5. 01003B Serious 19100269 N05 06/06/2000 06/10/2000 $0 $0 $0 06/29/2000 J - ALJ Decision  
6. 01004A Serious 19100269 M03 VI 06/06/2000 06/10/2000 $5,000 $5,000 $0 06/28/2000 J - ALJ Decision Citation has been deleted.
7. 01004B Serious 19100269 N02 06/06/2000 06/10/2000 $0 $0 $0 06/29/2000 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 638304
Event: 12/07/1999
BURN - ELECTRICAL FAULT

An employee was replacing an electric service. He was using a metal utility knife to cut through insulation on a deenergized 2400-volt conductor. The knife contacted an energized part and a grounded surface at the same time, causing an electrical fault. The employee received first- and second-degree burns over 60 percent of his body from the ensuing electric arc. He died from his injuries.

Keywords: BURN, CLOTHING, E GI II, ELEC PROTECT EQUIP, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109944702 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.