Powered by GoogleTranslate

Inspection Detail

Inspection: 109637579 - Techalloy Company, Inc.

Inspection Information - Office: Naperville Area Office

 

Inspection Nr: 109637579
Report ID: 0521400
Date Opened: 07/31/1991

Site Address:
Techalloy Company, Inc.
Jefferson And Olson Road
Union, IL 60180

Mailing Address:
P.O. Box 423, Union, IL 60180

Union Status: NonUnion

SIC:3315

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/07/1991

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 11/18/1991


Related Activity
Type Activity Nr Safety Health
Accident 360120877
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $4,000 $0 $0 $0 $0 $4,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100303 B01 09/09/1991 09/12/1991 $4,000 $5,000 $0 I - Informal Settlement  
2. 01001B Serious 19100304 A03 09/09/1991 09/12/1991 $0 $0 $0 I - Informal Settlement  
3. 01001C Serious 19100334 A02 II 09/09/1991 09/12/1991 $0 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 840884
Event: 07/31/1991
ELECTRIC SHOCK - GROUND FAULT IN CORD SET

AN EXTENSION CORD SET THAT WAS USED TO ENERGIZE A RESISTANCE WELDER (A BUTT WELDER) HAD BEEN IMPROPERLY WIRED. THE CORD SET WAS NOT MANUFACTURED, BUT WAS ASSEMBLED IN HOUSE BY UNQUALIFIED PERSONS. DURING THE INITIAL ASSEMBLY, THE CORD SET WAS WIRED CORRECTLY, EXCEPT THAT THE GREEN CONDUCTOR WAS USED AS A CURRENT-CARRYING CONDUCTOR, RATHER THAN AS THE EQUIPMENT GROUNDING CONDUCTOR. LATER, THE CORD CONNECTOR ON THE CORD SET WAS REPLACED. WHEN THIS WAS DONE, THE GREEN CONDUCTOR WAS CONNECTED TO THE EQUIPMENT GROUNDING TERMINAL. A CONTINUITY CHECK WAS NOT PERFORMED ON THE REPAIRED CORD SET. AN EMPLOYEE WAS ELECTROCUTED WHEN HE CONTACTED THE WELDER AFTER THE REPAIRED CORD SET WAS PLUGGED IN.

Keywords: ELECTRICAL, CORD SET, E GI VII, ELECTROCUTED, WELDER, GROUND FAULT, EQUIPMENT GROUNDING, UNTRAINED, EQUIPMENT APPROVAL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109637579 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close