Powered by GoogleTranslate

Inspection Detail

Inspection: 109618322 - R.J.M. Realty Inc.

Inspection Information - Office: Boston North Area Office

 

Inspection Nr: 109618322
Report ID: 0134000
Date Opened: 06/16/1993

Site Address:
R.J.M. Realty Inc.
Bld. #5, Marginal St.
Lowell, MA 01854

Mailing Address:
950 Broadway, Lowell, MA 01854

Union Status: NonUnion

SIC:1751

NAICS: 0 


Inspection Type: Referral

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/13/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 02/25/1994


Related Activity
Type Activity Nr Safety Health
Referral 901482067 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $3,900 $0 $0 $0 $0 $3,900
Current Penalty $2,700 $0 $0 $0 $0 $2,700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260403 I02 I 10/21/1993 10/26/1993 $375 $750 $0 I - Informal Settlement  
2. 01002 Serious 19260403 J02 I 10/21/1993 10/26/1993 $1,500 $1,500 $0 -  
3. 01003 Serious 19260405 A02 IIJ 10/21/1993 10/26/1993 $300 $600 $0 I - Informal Settlement  
4. 01004 Serious 19260405 G01 III 10/21/1993 10/26/1993 $225 $450 $0 I - Informal Settlement  
5. 01005 Serious 19260405 G02 IV 10/21/1993 10/26/1993 $300 $600 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 655290
Event: 06/16/1993
ELECTRIC SHOCK - CONTACT WITH ENERGIZED PARTS THRU WRENCH

Three employees were boarding up windows in a substation. Two of the employees were outside the building, cutting plywood sheets to size and drilling holes for U-bolts to hold the plywood securely to the metal window frames. The other employee was inside the building standing on a wooden stepladder, using a 203-millimeter crescent wrench to secure nuts to the U-bolts. An electric arc apparently jumped from an exposed 13.9-kilovolt fuse to the wrench or to the employee's arm. The employee suffered second- and third-degree burns from the arc. He was hospitalized for his injuries.

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC SHOCK, ELECTRICAL FAULT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109618322 Hospitalized injury Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.