Inspection Detail
Inspection: 109614594 - Rouse Tampa Inc.
Inspection Information - Office: Tampa Area Office
Site Address:
Rouse Tampa Inc.
3302 W. Mlk Blvd
Tampa, FL 33607
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:6512
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/30/1994
Emphasis:
Case Closed: 10/11/1994
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360820336 | ||
| Referral | 901676718 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 12 | 12 | ||||
| Current Violations | 12 | 12 | ||||
| Initial Penalty | $27,250 | $0 | $0 | $0 | $0 | $27,250 |
| Current Penalty | $27,250 | $0 | $0 | $0 | $0 | $27,250 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100147 C01 | 09/01/1994 | 10/04/1994 | $1,000 | $1,000 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100303 G02 I | 09/01/1994 | 10/04/1994 | $1,250 | $1,250 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19100304 E01 I | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 4. | 01004 | Serious | 19100304 E01 V | 09/01/1994 | 09/16/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 5. | 01005 | Serious | 19100332 B01 | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 6. | 01006 | Serious | 19100332 B02 | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 7. | 01007 | Serious | 19100332 C | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 8. | 01008 | Serious | 19100333 A | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 9. | 01009 | Serious | 19100333 B02 I | 09/01/1994 | 09/08/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 10. | 01010 | Serious | 19100335 A01 I | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 11. | 01011 | Serious | 19100335 A01 V | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement | ||
| 12. | 01012 | Serious | 19100335 A02 II | 09/01/1994 | 10/04/1994 | $2,500 | $2,500 | $0 | I - Informal Settlement |
Investigation Summary
A circuit breaker supplying an air conditioner on a roof had been opening for several days. Two heating, ventilation, and air conditioning employees were assigned to repair the problem, though neither of them was an electrician. They did not deenergize and lockout the circuit, and they were not wearing any personal protective equipment. The 480-volt circuit breaker was fed by a loop directly from a 13.2-kilovolt transformer. One of the two employees approached the circuit breaker panelboard, which had its cover and door removed some days before the accident. He either reset the faulty breaker or started to remove it, and an electrical fault occurred. Heat from the fault current melted the insulation on conductors at the block connection at the switchgear, causing another fault at this location. As a result of an electric arc from the primary fault, the employee near the circuit breaker sustained burns over 87 percent of his body. He was hospitalized for his injuries. As a result of an electric arc from the secondary fault, the other employee sustained burns over 50 percent of his body. He died from his injuries.
Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICAL WORK, CIRCUIT BREAKER, ELECTRICAL FAULT, SWITCHGEAR, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 109614594 | Hospitalized injury | Burn/Scald(Heat) | Heating, air conditioning, and refrig. mechanics | ||
| 2 | 109614594 | Fatality | Burn/Scald(Heat) | Heating, air conditioning, and refrig. mechanics |