Inspection Detail
Inspection: 109607424 - Florida Power & Light Company
Inspection Information - Office: Tampa Area Office
Site Address:
Florida Power & Light Company
510 Bay Isles Road
Longboat Key, FL 33548
Mailing Address:
1177 North Lime Ave., Sarasota, FL 34237
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/24/1994
Emphasis:
Case Closed: 07/19/1995
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361982234 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
| Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 5A0001 | 09/08/1994 | 10/11/1994 | $2,000 | $5,000 | $0 | 10/03/1994 | F - Formal Settlement |
Investigation Summary
A four-person power line crew had worked through the night to replace an underground circuit in a commercial area. The existing circuit was not working properly. The work was nearly complete, and the circuit was to be reenergized. To do this, a phasing meter was to measure and match the three phase conductors of the two circuits. The normal procedure for this part of the job called for a live-line phasing tool. However, the phasing meter the crew brought to the worksite was designed to be used only with insulated conductors. It was not designed as a live-line tool. When one of the crew members brought one end of the phasing meter into contact with an uninsulated, 13.2-kilovolt conductor, he was electrocuted.
Keywords: ELEC PROTECT EQUIP, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, UNDRGRD INSTALLATION, ELEC UTILITY WORK, UNDRGRD POWER LINE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 109607424 | Fatality | Electric Shock | Electrical power installers and repairers |