Powered by GoogleTranslate

Inspection Detail

Inspection: 109546465 - Tsi, Inc.

Inspection Information - Office: Englewood Area Office

 

Inspection Nr: 109546465
Report ID: 0830600
Date Opened: 03/31/1992

Site Address:
Tsi, Inc.
Hwy 194, 5 Miles E. Of N. Lajunta On Hwy 104
La Junta, CO 81050

Mailing Address:
12805 Weld Cty Rd. #2, Brighton, CO 80601

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 04/23/1992

Emphasis:

Case Closed: 12/02/1992


Related Activity
Type Activity Nr Safety Health
Accident 360979553
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 3 5
Current Violations 2 3 5
Initial Penalty $14,000 $0 $0 $0 $0 $14,000
Current Penalty $9,100 $0 $0 $0 $0 $9,100
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260556 B02 V 05/28/1992 06/07/1992 $4,550 $7,000 $0 I - Informal Settlement  
2. 01002 Serious 19260950 C02 I 05/28/1992 06/07/1992 $4,550 $7,000 $0 I - Informal Settlement  
3. 02001 Other 19260059 E01 05/28/1992 06/30/1992 $0 $0 $0 -  
4. 02002 Other 19260059 F05 I 05/28/1992 06/30/1992 $0 $0 $0 -  
5. 02003 Other 19260059 G01 05/28/1992 06/30/1992 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 525675
Event: 03/24/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

TWO POWER LINE WORKERS WERE WORKING FROM THE BUCKET OF AN AERIAL LIFT, INSTALLING SUSPENSION INSULATORS ON NEW, GROUNDED CONDUCTORS. THE OLD 7200-VOLT CONDUCTORS, WHICH REMAINED ENERGIZED, HAD BEEN MOVED LATERALLY ONTO AUXILIARY CROSSARMS. ONE OF THE EMPLOYEES, WHO WAS NOT USING ELECTRICAL PROTECTIVE EQUIPMENT, REACHED OVER THE NEW CONDUCTOR AND POINTED TOWARD AN OLD CONDUCTOR, CONTACTING IT WITH HIS HAND. THE NEW CONDUCTOR WAS ALSO CONTACTING THE EMPLOYEE, BENEATH HIS ARMPIT. THE POWER LINE WORKER WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109546465 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.