Inspection Detail
Inspection: 109257816 - Delta Electric Power Association
Inspection Information - Office: Jackson Area Office
Site Address:
Delta Electric Power Association
Stanford Road (Off Hwy 82)
Carrollton, MS 38917
Mailing Address:
1700 Highway 82 West, Greenwood, MS 38930
Union Status: NonUnion
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/21/1994
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/20/1994
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360794309 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 4 | 4 | ||||
Current Violations | 4 | 4 | ||||
Initial Penalty | $2,500 | $0 | $0 | $0 | $0 | $2,500 |
Current Penalty | $2,500 | $0 | $0 | $0 | $0 | $2,500 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260950 B01 | 10/03/1994 | 10/14/1994 | $625 | $625 | $0 | - | ||
2. | 01002 | Serious | 19260955 C03 | 10/03/1994 | 10/06/1994 | $625 | $625 | $0 | - | ||
3. | 01003 | Serious | 19260955 C04 I | 10/03/1994 | 10/06/1994 | $625 | $625 | $0 | - | ||
4. | 01004 | Serious | 19260955 C05 | 10/03/1994 | 10/06/1994 | $625 | $625 | $0 | - |
Investigation Summary
A power line worker was removing one 4/0 ACSR phase conductor of a three-phase, Y-connected overhead power line (13.2 kilovolts phase to phase, 7620 volts phase to ground). The conductor had been deenergized the previous day, and it had fallen into some trees. The power line worker retrieved the conductor from the trees. Carrying the conductor on his shoulder and holding it with both hands, the employee took four to six steps. The conductor contacted the lower remaining energized phase conductor, and the worker was electrocuted. He was found lying face down, still grasping the conductor in both hands with the conductor over his shoulder.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 109257816 | Fatality | Electric Shock | Electrical power installers and repairers |