Inspection Detail
Inspection: 109257261 - H. B. Zachry Company
Inspection Information - Office: Jackson Area Office
Site Address:
H. B. Zachry Company
International Paper, 61 Carthage Point Road
Natchez, MS 39120
Mailing Address:
P. O. Box 17710, Natchez, MS 39122
Union Status: NonUnion
SIC:1541
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/21/1995
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/22/1996
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361091978 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $17,000 | $0 | $0 | $0 | $0 | $17,000 |
| Current Penalty | $14,000 | $0 | $0 | $0 | $0 | $14,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260416 A01 | 01/08/1996 | 01/11/1996 | $7,000 | $5,000 | $0 | 02/01/1996 | F - Formal Settlement | |
| 2. | 01002 | Serious | 19260416 A03 | 01/08/1996 | 01/11/1996 | $7,000 | $7,000 | $0 | 02/01/1996 | F - Formal Settlement | |
| 3. | 01003 | Serious | 19260416 G07 | 01/08/1996 | 01/11/1996 | $5,000 | $5,000 | $0 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
A four-person electrical crew was working in a restricted access electrical control center at a paper mill. The crew was removing a 4160-volt, three-phase distribution panel from service at the north end of the control center. The employees were then going to pull and cut the supply cable and reroute it into a new cable tray and then into a new panel at the south end of the control center. Two employees were working on the mezzanine level (the reactor floor), which covered about one half of the length of the center. The distribution panel to be dismantled had been deenergized, locked out, and tested with a high-voltage tester. One cable of the set of three phase cables had been cut. Before starting to pull the large heavy cable out of the tray, the lead electrician wanted to confirm that it was the right cable tray, so he walked to edge of the floor near three unguarded, energized, 4160-volt, three-phase reactors to talk to another electrician on the floor below. As he was turning to move away from the floor edge, the lead electrician touched an uninsulated portion of the reactor-busbar connection with his arm and was electrocuted. (He subsequently fell to the floor below.)
Keywords: ELEC PROTECT EQUIP, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, BUSBAR, ELECTRICAL WORK, LOCKOUT, E C, INATTENTION
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 109257261 | Fatality | Electric Shock | Electricians |