Inspection Detail
Inspection: 109205799 - Southeast Power Corporation
Inspection Information - Office: Tampa Area Office
Site Address:
Southeast Power Corporation
Structure A122w5 Line #2 Brevard To Malabar
Rockledge, FL 32955
Mailing Address:
1805 Hammock Road, Titusville, FL 32796
Union Status: NonUnion
SIC:4931
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 12/15/1997
Emphasis:
Case Closed: 02/05/1998
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 361088420 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $2,500 | $0 | $0 | $0 | $0 | $2,500 |
Current Penalty | $2,500 | $0 | $0 | $0 | $0 | $2,500 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100269 M03 VI | 01/12/1998 | 01/15/1998 | $2,500 | $2,500 | $0 | - |
Investigation Summary
A five-person power line crew was replacing insulators and crossarms, where needed, on a deenergized, 230-kilovolt overhead power line. An energized 230-kilovolt overhead power line was located about 15.2 meters to the north of the deenergized line. Two power line workers were in a Hi-Ranger aerial lift, getting in position to lift the middle, and last, phase conductor into place on an insulator attached to the crossarm of the structure supporting the power line. One of the two employee picked up the phase conductor with one arm, and the grounding conductor, which was located on the cross brace of the structure, with the other arm. He was electrocuted by current induced in the deenergized line. The line conductors had not been bonded or grounded.
Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK, AERIAL LIFT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 109205799 | Fatality | Electric Shock | Electrical power installers and repairers |