Powered by GoogleTranslate

Inspection Detail

Inspection: 109205799 - Southeast Power Corporation

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 109205799
Report ID: 0420600
Date Opened: 11/25/1997

Site Address:
Southeast Power Corporation
Structure A122w5 Line #2 Brevard To Malabar
Rockledge, FL 32955

Mailing Address:
1805 Hammock Road, Titusville, FL 32796

Union Status: NonUnion

SIC:4931

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/15/1997

Emphasis:

Case Closed: 02/05/1998


Related Activity
Type Activity Nr Safety Health
Accident 361088420
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $2,500 $0 $0 $0 $0 $2,500
Current Penalty $2,500 $0 $0 $0 $0 $2,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 M03 VI 01/12/1998 01/15/1998 $2,500 $2,500 $0 -  

Investigation Summary

Investigation Nr: 202287900
Event: 11/24/1997
ELECTRIC SHOCK - INDUCED CURRENT IN DEENERGIZED POWER LINE

A five-person power line crew was replacing insulators and crossarms, where needed, on a deenergized, 230-kilovolt overhead power line. An energized 230-kilovolt overhead power line was located about 15.2 meters to the north of the deenergized line. Two power line workers were in a Hi-Ranger aerial lift, getting in position to lift the middle, and last, phase conductor into place on an insulator attached to the crossarm of the structure supporting the power line. One of the two employee picked up the phase conductor with one arm, and the grounding conductor, which was located on the cross brace of the structure, with the other arm. He was electrocuted by current induced in the deenergized line. The line conductors had not been bonded or grounded.

Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109205799 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close