Inspection Detail
Inspection: 109081877 - U.S. Marine Corps
Inspection Information - Office: Raleigh Area Office
Site Address:
U.S. Marine Corps
Marine Corps Air Station
Cherry Point, NC 28533
Mailing Address:
, , 00000
Union Status: Union
SIC:9711
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership:
Safety/Health: Safety
Close Conference: 07/23/1993
Emphasis:
Case Closed: 02/14/1994
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360144786 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 6 | 6 | ||||
| Current Violations | 5 | 5 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19260020 B01 | 11/26/1993 | 01/31/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 2. | 01001B | Serious | 19260020 B02 | 11/26/1993 | 01/31/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 3. | 01001C | Serious | 19260021 B02 | 11/26/1993 | 01/31/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 4. | 01002 | Serious | 19260416 A01 | 11/26/1993 | 01/31/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 5. | 01003 | Serious | 19260950 B01 | 11/26/1993 | 01/31/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 6. | 01004 | Serious | 19260950 B02 | 11/26/1993 | 01/31/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 7. | 01005 | Serious | 19260950 C01 | 11/26/1993 | 01/31/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 8. | 01006 | Serious | 19260952 B02 | 11/26/1993 | 12/15/1993 | $0 | $0 | $0 | I - Informal Settlement | Citation has been deleted. |
Investigation Summary
Two power line workers were replacing a 50-kilovolt-ampere transformer on a 30-foot-tall utility pole. The employees were working from an insulated aerial lift. The 12470/7200-volt primary overhead power line was disconnected from the transformers by opening fused cutouts on the pole. One of the employees contacted the energized primary and then touched the ungrounded transformer on which the other employee was working. Both employees received severe electric shocks and were hospitalized. The employee who had been working on the transformer died of cardiac arrest 2 days after the accident.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 109081877 | Hospitalized injury | Electric Shock | Electrical power installers and repairers | ||
| 2 | 109081877 | Fatality | Electric Shock | Electrical power installers and repairers |