Powered by GoogleTranslate

Inspection Detail

Inspection: 109059790 - Southwest Electric Company

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 109059790
Report ID: 0627700
Date Opened: 07/14/1993

Site Address:
Southwest Electric Company
6501 S. E. 74th Street
Oklahoma City, OK 73135

Mailing Address:
P.O. Box 82639, Oklahoma City, OK 73135

Union Status: Union

SIC:3612

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/23/1993

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 09/27/1993


Related Activity
Type Activity Nr Safety Health
Accident 361146764
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $10,500 $0 $0 $0 $0 $10,500
Current Penalty $5,250 $0 $0 $0 $0 $5,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100147 C01 08/13/1993 09/15/1993 $1,375 $2,750 $0 I - Informal Settlement  
2. 01001B Serious 19100147 C04 II 08/13/1993 09/05/1993 $0 $0 $0 I - Informal Settlement Citation has been deleted.
3. 01002 Serious 19100147 C06 I 08/13/1993 09/15/1993 $1,375 $2,750 $0 I - Informal Settlement  
4. 01003A Serious 19100333 A 08/13/1993 08/18/1993 $2,500 $5,000 $0 I - Informal Settlement  
5. 01003B Serious 19100333 C07 08/13/1993 08/18/1993 $0 $0 $0 I - Informal Settlement  
6. 01003C Serious 19100333 C09 08/13/1993 08/18/1993 $0 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14241871
Event: 07/13/1993
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED CONDUCTOR

An employee was assigned to clean the top of a 17-foot, 1-inch-high oven and to lubricate the oven's motors. The rail and runway conductors for a bridge crane were located 19.5 feet above the floor, directly over the oven. The clearance between the top of the oven and the 480-volt, three-phase runway conductors was only 29 inches. As he was descending from the top of the oven, the employee stooped to go under the rail and, with his left hand, grabbed the runway conductors to maintain his balance. He was electrocuted.

Keywords: E GI IV, ELECTRICAL, ELECTROCUTED, RUNWAY CONDUCTOR, LOCKOUT, UNGUARDED LIVE PARTS, UNTRAINED, WORK SURFACE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109059790 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close