Powered by GoogleTranslate

Inspection Detail

Inspection: 109058438 - Public Service Of Oklahoma

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 109058438
Report ID: 0627700
Date Opened: 04/22/1993

Site Address:
Public Service Of Oklahoma
Old Hwy 81 And Refinery Road
Duncan, OK 73553

Mailing Address:
P. O. Box 201, 612 E. 6th St., Tulsa, OK 74102

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 06/22/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 08/12/1994


Related Activity
Type Activity Nr Safety Health
Referral 901460014 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations
Initial Penalty $3,250 $0 $0 $0 $0 $3,250
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 07/01/1993 07/06/1993 $1,625 $1,625 $0 07/23/1993 F - Formal Settlement Citation has been deleted.
2. 01001B Serious 19260950 B03 07/01/1993 07/06/1993 $0 $0 $0 07/23/1993 F - Formal Settlement Citation has been deleted.
3. 01002 Serious 19260950 C01 07/01/1993 07/06/1993 $1,625 $1,625 $0 07/23/1993 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 14241863
Event: 04/22/1993
BURN - ELECTRICAL FAULT IN METER

Three power line workers for an electric utility were performing preliminary work on a 34-kilovolt distribution circuit that was to be replaced by a 13.2-kilovolt circuit. The employees were testing the transformer secondaries with a rotation meter to determine the phase sequence of the transformers' loads. One of the crew members (employee #2) had just connected the meter, which was rated at 600 volts, to the 2300-volt output. His two coworkers were observing the operation. The underrated meter failed, initiating a phase-to-phase electrical fault. The ensuing electric arc burned the three employees and ignited their clothing (which resulted in further burn injuries). Employees #1 and #2 sustained second- and third-degree burns. The third employee sustained second-degree burns. The employee using the meter thought that the voltage was 480 volts. His coworkers did not inform him of the actual voltage and did not recognize the hazards involved with using the underrated meter.

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, TEST EQUIPMENT, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109058438 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
2 109058438 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
3 109058438 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close