Inspection Detail
Inspection: 108964347 - Ga Power Company
Inspection Information - Office: Atlanta West Area Office
Site Address:
Ga Power Company
Wages Mill Road Off Highway 16
Newnan, GA 30263
Mailing Address:
333 Piedmont Ave P.O. Box 4545, Atlanta, GA 30302
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/19/1995
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 10/31/1995
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360823736 |
Investigation Summary
A power line crew was working on a deenergized 115-kilovolt overhead power line. Three other energized overhead power lines of 115 to 230 kilovolts ran parallel to the deenergized line. One of the crew members removed one end of a protective ground from a phase conductor and, though it was apparently still connected to the first phase conductor, placed it in the aerial bucket with him. Using a live-line tool, he then removed the other end of the protective ground, which was connected to the pole band. He disconnected the ground from the live-line tool and was electrocuted. The grounding jumper was still connected to the first phase conductor, which was energized by induced voltage from the parallel lines. Apparently, the employee was standing on this jumper, which was lying in the bucket, as he removed the ground from the live-line tool.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 108964347 | Fatality | Electric Shock | Electrical power installers and repairers |