Powered by GoogleTranslate

Inspection Detail

Inspection: 108916347 - Malone Lumber, Inc

Inspection Information - Office: Baton Rouge Area Office

 

Inspection Nr: 108916347
Report ID: 0625700
Date Opened: 09/11/1991

Site Address:
Malone Lumber, Inc
7019 Division St
Merryville, LA 70653

Mailing Address:
P. O. Box 548, Merryville, LA 70653

Union Status: NonUnion

SIC:2421

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/11/1991

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 01/16/1992


Related Activity
Type Activity Nr Safety Health
Accident 361127434
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations
Initial Penalty $6,000 $0 $0 $0 $0 $6,000
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100332 B01 12/11/1991 12/20/1991 $3,000 $3,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19100334 A02 I 12/11/1991 12/16/1991 $3,000 $3,000 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 14414148
Event: 09/09/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH LIVE CONDUCTOR

TWO EMPLOYEES WERE REPAIRING A WOOD CHIP AND SAWDUST CONVEYOR AT A SAWMILL. THEY WERE WELDING AND CUTTING IN A HOLE LOCATED BENEATH THE CONVEYOR WHERE IT WAS JAMMED. THE HAZARDOUS ENERGY SOURCES FOR THE CONVEYOR HAD BEEN PROPERLY LOCKED OUT, AND THE ONLY SOURCE OF ELECTRICITY IN THE HOLE WAS A DROP LIGHT CONNECTED BY AN EXTENSION CORD SET TO A RECEPTACLE ON THE PERMANENT WIRING OF THE SAWMILL. THE PORTABLE LIGHT WAS GROUNDED; HOWEVER, EXAMINATION OF THE LIGHT'S POWER SUPPLY CORD REVEALED A SLIGHT SPLIT IN ITS INSULATION, WITH THE COPPER CONDUCTOR VISIBLE. IT WAS DAMP IN THE HOLE FROM THE WETTING OF THE WOOD CHIPS IN THE PROCESS. THE TWO EMPLOYEES HAD FINISHED FOR THE DAY. WHEN SECOND OF THE TWO EMPLOYEES BACKED OUT OF THE HOLE, HE LET OUT A MUFFLED CRY. ANOTHER EMPLOYEE GRABBED HIM BY THE LEGS AND FELT AN ELECTRIC SHOCK. THE EMPLOYEE IN THE HOLE HAD BEEN ELECTROCUTED. (THE EMPLOYEE WHO RECEIVED THE ELECTRIC SHOCK WAS NOT LISTED ON AN INJURY LINE IN THE ORIGINAL REPORT.)

Keywords: E GI V, ELEC INSULATION, ELECTRICAL, ELECTROCUTED, ELECTRIC CONDUCTOR, ELECTRIC CORD, ELECTRIC LIGHT--PORT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 108916347 Fatality Electric Shock Not specified mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.