Inspection Detail
Inspection: 108866336 - K L Bradley Electric
Inspection Information - Office: Oklahoma City Area Office
Site Address:
K L Bradley Electric
1100 N W 32rd Street
Okla City, OK 73112
Mailing Address:
P. O. Box 23392, Okla City, OK 73123
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/25/1995
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 02/29/1996
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360691299 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
| Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19260416 A01 | 10/05/1995 | 10/09/1995 | $0 | $5,000 | $0 | 10/27/1995 | F - Formal Settlement | |
| 2. | 01001B | Serious | 19260417 D01 | 10/05/1995 | 11/07/1995 | $2,000 | $0 | $0 | 10/27/1995 | F - Formal Settlement |
Investigation Summary
An electrician was to move a 120-volt switch circuit from inside an office to an outside wall. He removed a lighting panel in the office and climbed into the attic space above. He pulled the conduit for the fan switch over to the junction box. With the circuit energized, he then pulled the new conductors to the switch box through the existing conduit for the 277-volt lighting circuit. He next started installing a combination switch, which allows a person to control the light independently from the fan. The employee failed to break off a tab on the switch to separate the poles. This allowed the black conductor to remain energized. It is believed that the electrician was electrocuted when he cut into the black or red conductor to make up the circuit.
Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRIC SWITCH, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 108866336 | Fatality | Electric Shock | Electricians |
Translate