Powered by GoogleTranslate

Inspection Detail

Inspection: 108224288 - Electrical Construction Company

Inspection Information - Office: Or-E-Salem 1054100

 

Inspection Nr: 108224288
Report ID: 1054113
Date Opened: 05/24/1990

Site Address:
Electrical Construction Company
15995 Sw Walker Rd
Beaverton, OR 97006

Mailing Address:
Po Box 10286, Portland, OR 97210

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/19/1990

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 12/21/1990


Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $0 $12,500 $0 $0 $0 $12,500
Current Penalty $0 $7,500 $0 $0 $0 $7,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Willful 19260416 A01 07/03/1990 05/24/1990 $3,000 $5,000 $0 07/13/1990 L - State Settlement  
2. 01002 Willful 740003002 C 07/03/1990 07/06/1990 $4,500 $7,500 $0 07/13/1990 L - State Settlement  

Investigation Summary

Investigation Nr: 676833
Event: 05/24/1990
BURN - ELECTRICAL FAULT IN ELECTRICAL CABINET

Two electricians were routing conductors behind the vertical busbars of a large floor-mounted, high-ampacity circuit breaker cabinet. As of them fed a grounding conductor to his coworker, the conductor slipped and contacted one of the 277-volt busbars, which had not been deenergized. A phase-to-phase electrical fault occurred, and the ensuing electric arc burned both employees. One of the injured employees was able to use a portable telephone to call for assistance under his employer's emergency plan. The employees were hospitalized at a burn center.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, BUSBAR, ELECTRICAL WORK, LOCKOUT, ELECTRICAL CABINET, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 108224288 Hospitalized injury Burn/Scald(Heat) Supervisors; electricians & power transm. install.
2 108224288 Hospitalized injury Burn/Scald(Heat) Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close