Inspection Detail
Inspection: 107930646 - Hunter Corporation
Inspection Information - Office: Indiana Department Of Labor
Site Address:
Hunter Corporation
Bailey Generating Station 246 Bailly Station Rd
Chesterton, IN 46304
Mailing Address:
, , 00000
Union Status: Union
SIC:1711
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/01/1990
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 07/30/1990
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360471106 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 5 | 5 | ||||
| Current Violations | 5 | 5 | ||||
| Initial Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
| Current Penalty | $4,000 | $0 | $0 | $0 | $0 | $4,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 2200080101 | 06/25/1990 | 06/29/1990 | $1,000 | $1,000 | $0 | - | ||
| 2. | 01001B | Serious | 19260021 B02 | 06/29/1990 | 06/25/1990 | $0 | $0 | $0 | - | ||
| 3. | 01002A | Serious | 19260028 A | 06/25/1990 | 06/29/1990 | $1,000 | $1,000 | $0 | - | ||
| 4. | 01002B | Serious | 19260451 I08 | 06/25/1990 | 06/29/1990 | $0 | $0 | $0 | - | ||
| 5. | 01004 | Serious | 19260351 B04 | 06/25/1990 | 06/29/1990 | $500 | $1,000 | $0 | I - Informal Settlement | ||
| 6. | 01005 | Serious | 19260451 A06 | 06/25/1990 | 06/29/1990 | $500 | $1,000 | $0 | I - Informal Settlement | ||
| 7. | 01006A | Serious | 19260451 I05 | 06/25/1990 | 06/29/1990 | $1,000 | $1,000 | $0 | - | ||
| 8. | 01006B | Serious | 19260451 I08 IV | 06/25/1990 | 06/29/1990 | $0 | $0 | $0 | - | ||
| 9. | 01006C | Serious | 19260451 I07 | 06/25/1990 | 06/29/1990 | $0 | $0 | $0 | - |
Investigation Summary
At approximately 12:15 a.m. on January 8, 1990, Employees #1, #2, and #3 were arc welding boiler water wall panels from a two-point suspended scaffold. Employees #1 and #2 were not using safety belts. A failure in the manufactured spliced eyelet of the wire rope suspension caused the scaffold to fall freely on one side while remaining suspended on the other side. Employee #1 fell approximately 90 ft, suffered multiple injuries, and died immediately. Employee #2 also fell 90 ft and suffered multiple injuries; he died the next day. Employee #3 said his safety belt was anchored to the outside guardrail. The guardrail broke free from the falling scaffold and was inadvertently suspended by an approximately 30 ft long orange extension cord. Employee #3 was not seriously injured. Employee #4 sustained a bruised shoulder from debris that fell approximately 90 ft and struck him as he worked on an elevated scaffold floor in the 27 ft by 36 ft by 130 ft boiler fire box. The 3/4 in. secondary manila rope suspension was either not attached or improperly tied, which allowed the scaffold to fall freely. The wire rope eyelet damage was caused by an electrical current. There was no ground conductor from the stage to the structure. The rubber insulator on the eyelet had a hole in it where the damage occurred.
Keywords: ELECTRIC ARC, WIRE ROPE, SAFETY BELT, BROKEN CABLE, CONSTRUCTION, EQUIPMENT FAILURE, SCAFFOLD COLLAPSE, FALL, ARC WELDING, SCAFFOLD
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 107930646 | Fatality | Other | Plumbers, pipefitters and steamfitters | ||
| 2 | 107930646 | Fatality | Other | Plumbers, pipefitters and steamfitters | ||
| 3 | 107930646 | Non Hospitalized injury | Other | Plumbers, pipefitters and steamfitters | ||
| 4 | 107930646 | Non Hospitalized injury | Bruise/Contus/Abras | Plumbers, pipefitters and steamfitters |
Translate