Powered by GoogleTranslate

Inspection Detail

Inspection: 107929648 - R & R Plastics

Inspection Information - Office: Indiana Department Of Labor

 

Inspection Nr: 107929648
Report ID: 0551800
Date Opened: 08/10/1989

Site Address:
R & R Plastics
4th Rd, Kingsbury Industrial Park
Kingsbury, IN 46345

Mailing Address:
Po Box 303, Kingsbury, IN 46345

Union Status: NonUnion

SIC:3082

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/18/1989

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 11/09/1989


Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $2,000 $0 $0 $2,000
Current Penalty $0 $0 $1,500 $0 $0 $1,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Repeat 19100304 F04 10/27/1989 10/30/1989 $1,500 $2,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 981209
Event: 08/10/1989
ELECTRIC SHOCK - GROUND FAULT IN PLASTIC MOLDING MACHINE

AN EMPLOYEE WAS INSTALLING A WATER HEATER (IMS, SERIAL NO. 523853616) ON A TOSHIBA MODEL ISE 170-9A PLASTIC INJECTOR MOLDING MACHINE (SERIAL NO. 557702). THE EXISTING WATER HEATER APPARENTLY DEVELOPED A GROUND FAULT WHEN THE HEATING COIL FAILED. THE WATER HEATER, WHICH WAS CONNECTED BY A FLEXIBLE CORD OFF A PIGTAIL FROM THE MOLDING MACHINE, WAS WIRED CORRECTLY, EXCEPT THAT THE EQUIPMENT GROUNDING CONDUCTOR ON THE PIGTAIL HAD NOT BEEN CONNECTED. THE MOLDING MACHINE AND THE WATER HEATER WERE SUPPLIED BY A 3-PHASE, 480-VOLT, 100-AMPERE CIRCUIT. THE FUSES PROTECTING THE CIRCUIT DID NOT OPEN ON THE GROUND FAULT. THE EMPLOYEE TOUCHED THE ENERGIZED PORTION OF THE WATER HEATER WHILE HE WAS IN CONTACT WITH THE GROUNDED MOLDING MACHINE. THE EMPLOYEE WAS ELECTROCUTED. HE HAD BURN MARKS ON HIS RIGHT HAND AND ON HIS LEGS ABOVE THE KNEES.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107929648 Fatality Electric Shock Machinery maintenance occupations
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close