Powered by GoogleTranslate

Inspection Detail

Inspection: 107816118 - Collins Electrical Const. Co., St. Paul

Inspection Information - Office: Minnesota Department Of Labor And Industry

 

Inspection Nr: 107816118
Report ID: 0552700
Date Opened: 10/17/1988

Site Address:
Collins Electrical Const. Co., St. Paul
177 East Fillmore
St. Paul, MN 55107

Mailing Address:
278 State St., St. Paul, MN 55107

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/01/1988

Emphasis:

Case Closed: 03/20/1995


Related Activity
Type Activity Nr Safety Health
Accident 360239024
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $6,192 $0 $0 $0 $0 $6,192
Current Penalty $3,096 $0 $0 $0 $0 $3,096
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A 1 11/21/1988 11/24/1988 $3,096 $6,192 $0 12/20/1988 R - Review Commission  

Investigation Summary

Investigation Nr: 998542
Event: 10/14/1988
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED BUSBAR

AN ELECTRICIAN WAS INSTALLING FEEDERS FOR FIRE PUMP CIRCUITS AT THE MAIN FIRE PUMP PANELBOARD ON THE FIRST FLOOR OF A BUILDING. ALL THE DOWNSTREAM PANELBOARDS WERE DEENERGIZED, AND THE 2000-AMPERE, 480/277-VOLT MAIN PANELBOARD WAS ALSO DEENERGIZED, EXCEPT FOR THE MAIN BUSBARS FOR THE SERVICE ENTRANCE CONDUCTORS. THESE BUSBARS WERE LOCATED BEHIND THE PANEL'S FRAME CHANNELS, ABOUT 7 INCHES BELOW THE TOP OF THE MIDDLE COVER. THE ELECTRICIAN HAD FED THREE SINGLE-PHASE FEEDERS FROM THE DOWNSTREAM PANELBOARDS TO THE BOTTOM OF THE MAIN PANELBOARD. THESE CONDUCTORS WERE BROUGHT IN THROUGH THE PANELBOARD AND CONNECTED TO LUGS NEAR THE BOTTOM OF THE PANEL THAT WERE TO BE ENERGIZED AT A LATER TIME. APPARENTLY, AFTER BRINGING THE CONDUCTORS INTO THE PANELBOARD, THE ELECTRICIAN REACHED BEHIND THE PANELBOARD'S OPEN TOP COVER TO ATTACH A CABLE TIE. IN DOING THIS, HE CONTACTED THE ENERGIZED BUSBAR AND WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VI, BUSBAR, ELEC PROTECT EQUIP, ELECTRICIAN, ELECTROCUTED, PANELBOARD, ELECTRICAL WORK, LOCKOUT, BLIND REACHING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107816118 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close