Inspection Detail
Inspection: 107816100 - Kraus-Anderson Construction - St. Paul
Inspection Information - Office: Minnesota Department Of Labor And Industry
Site Address:
Kraus-Anderson Construction - St. Paul
177 East Fillmore
St. Paul, MN 55107
Mailing Address:
200 Grand Avenue, St. Paul, MN 55102
Union Status: Union
SIC:1542
NAICS: 0
Inspection Type: Unprog Rel
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/17/1988
Emphasis:
Case Closed: 11/17/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360239024 |
Investigation Summary
AN ELECTRICIAN WAS INSTALLING FEEDERS FOR FIRE PUMP CIRCUITS AT THE MAIN FIRE PUMP PANELBOARD ON THE FIRST FLOOR OF A BUILDING. ALL THE DOWNSTREAM PANELBOARDS WERE DEENERGIZED, AND THE 2000-AMPERE, 480/277-VOLT MAIN PANELBOARD WAS ALSO DEENERGIZED, EXCEPT FOR THE MAIN BUSBARS FOR THE SERVICE ENTRANCE CONDUCTORS. THESE BUSBARS WERE LOCATED BEHIND THE PANEL'S FRAME CHANNELS, ABOUT 7 INCHES BELOW THE TOP OF THE MIDDLE COVER. THE ELECTRICIAN HAD FED THREE SINGLE-PHASE FEEDERS FROM THE DOWNSTREAM PANELBOARDS TO THE BOTTOM OF THE MAIN PANELBOARD. THESE CONDUCTORS WERE BROUGHT IN THROUGH THE PANELBOARD AND CONNECTED TO LUGS NEAR THE BOTTOM OF THE PANEL THAT WERE TO BE ENERGIZED AT A LATER TIME. APPARENTLY, AFTER BRINGING THE CONDUCTORS INTO THE PANELBOARD, THE ELECTRICIAN REACHED BEHIND THE PANELBOARD'S OPEN TOP COVER TO ATTACH A CABLE TIE. IN DOING THIS, HE CONTACTED THE ENERGIZED BUSBAR AND WAS ELECTROCUTED.
Keywords: ELECTRICAL, E GI VI, BUSBAR, ELEC PROTECT EQUIP, ELECTRICIAN, ELECTROCUTED, PANELBOARD, ELECTRICAL WORK, LOCKOUT, BLIND REACHING
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 107816100 | Occupation Not Listed |