Accident 360239024

Investigation Summary

Investigation Nr: 998542
Event: 10/14/1988
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED BUSBAR

AN ELECTRICIAN WAS INSTALLING FEEDERS FOR FIRE PUMP CIRCUITS AT THE MAIN FIRE PUMP PANELBOARD ON THE FIRST FLOOR OF A BUILDING. ALL THE DOWNSTREAM PANELBOARDS WERE DEENERGIZED, AND THE 2000-AMPERE, 480/277-VOLT MAIN PANELBOARD WAS ALSO DEENERGIZED, EXCEPT FOR THE MAIN BUSBARS FOR THE SERVICE ENTRANCE CONDUCTORS. THESE BUSBARS WERE LOCATED BEHIND THE PANEL'S FRAME CHANNELS, ABOUT 7 INCHES BELOW THE TOP OF THE MIDDLE COVER. THE ELECTRICIAN HAD FED THREE SINGLE-PHASE FEEDERS FROM THE DOWNSTREAM PANELBOARDS TO THE BOTTOM OF THE MAIN PANELBOARD. THESE CONDUCTORS WERE BROUGHT IN THROUGH THE PANELBOARD AND CONNECTED TO LUGS NEAR THE BOTTOM OF THE PANEL THAT WERE TO BE ENERGIZED AT A LATER TIME. APPARENTLY, AFTER BRINGING THE CONDUCTORS INTO THE PANELBOARD, THE ELECTRICIAN REACHED BEHIND THE PANELBOARD'S OPEN TOP COVER TO ATTACH A CABLE TIE. IN DOING THIS, HE CONTACTED THE ENERGIZED BUSBAR AND WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VI, BUSBAR, ELEC PROTECT EQUIP, ELECTRICIAN, ELECTROCUTED, PANELBOARD, ELECTRICAL WORK, LOCKOUT, BLIND REACHING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107816100 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.