Powered by GoogleTranslate

Inspection Detail

Inspection: 107734386 - Lee Davis Electric, Inc.

Inspection Information - Office: Minnesota Department Of Labor And Industry

 

Inspection Nr: 107734386
Report ID: 0552700
Date Opened: 08/27/1993

Site Address:
Lee Davis Electric, Inc.
Hwy 71 S
Park Rapids, MN 56470

Mailing Address:
Rt 1, Box 2a, Park Rapids, MN 56470

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/27/1993

Emphasis:

Case Closed: 03/03/1994


Related Activity
Type Activity Nr Safety Health
Accident 360241541
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 2 2 4
Initial Penalty $522 $0 $0 $290 $0 $812
Current Penalty $522 $0 $0 $290 $0 $812
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 10/20/1993 12/22/1993 $261 $261 $0 -  
2. 01002 Serious 5207060001 10/20/1993 12/22/1993 $261 $261 $0 -  
3. 02001 Other 182065308 10/20/1993 12/22/1993 $0 $0 $0 -  
4. 02002 Other 5210063001 10/20/1993 10/24/1993 $290 $290 $0 -  

Investigation Summary

Investigation Nr: 813923
Event: 08/27/1993
ELECTRIC SHOCK - GROUND FAULT IN CONVEYOR CIRCUIT

A JOURNEYMAN ELECTRICIAN WAS TROUBLESHOOTING A 480-VOLT CONTROL CIRCUIT FOR A CONVEYOR SYSTEM. THE CONVEYOR WAS USED TO RECEIVE AND PILE POTATOES AT A WAREHOUSE. THE ELECTRICIAN HAD REPLACED THREE MALFUNCTIONING COMPONENTS AND HAD RECONNECTED THE PLUG ON THE CONVEYOR'S POWER SUPPLY CABLE. HE THEN WENT TO THE CONTROL STATION AT THE RECEIVING END OF THE CONVEYOR AND GRABBED THE HAND GRIP THAT WAS PROVIDED TO AID EMPLOYEES CLIMBING ONTO THE CONTROL PLATFORM. HE WAS ELECTROCUTED AS HE TOUCHED THE HAND GRIP. (THE CONVEYOR, WHICH WAS MOUNTED COMPLETELY ON RUBBER TIRES, WAS ISOLATED FROM GROUND.) INVESTIGATION REVEALED THAT A GREEN-COLORED CONDUCTOR HAD BEEN USED AS A 277-VOLT CIRCUIT CONDUCTOR. AN UNSKILLED EMPLOYEE HAD ERRONEOUSLY CONNECTED THIS CONDUCTOR TO TWO GREEN EQUIPMENT GROUNDING CONDUCTORS WITH A WIRE NUT AS HE WAS REPLACING A DAMAGED JUNCTION BOX. THE EQUIPMENT GROUNDING CONDUCTORS WERE CONNECTED TO THE FRAME OF THE CONVEYOR. WHEN THE CONVEYOR WAS ENERGIZED, THIS GROUND FAULT ALSO ENERGIZED THE CONVEYOR'S FRAME.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, CONVEYOR, EQUIPMENT GROUNDING, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107734386 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.