Inspection Detail
Inspection: 107732844 - Minnesota Valley Coop Light & Power Assocation
Inspection Information - Office: Minnesota Department Of Labor And Industry
Site Address:
Minnesota Valley Coop Light & Power Assocation
501 S. 1st Street
Montevideo, MN 56265
Mailing Address:
P O Box 717, Montevideo, MN 56265
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/29/1988
Emphasis:
Case Closed: 03/14/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360316400 |
Investigation Summary
A LINE WORKER WAS THE SENIOR EMPLOYEE IN CHARGE OF A THREE-MAN LINE CREW ASSIGNED TO REPLACE TWELVE OIL CIRCUIT BREAKERS IN A DISTRUBUTION SUBSTATION. THE THREE EMPLOYEES HAD ALREADY REPLACED ONE THREE-PHASE BANK OF OIL CIRCUIT BREAKERS WITHIN THE SUBSTATION. BEFORE WORK WAS PERFORMED ON THE OIL CIRCUIT BREAKERS, THE UNITS WERE BYPASSED AND DEENERGIZED. RUBBER INSULATING GLOVES WERE USED, AS REQUIRED BY COMPANY POLICY. AS ONE EMPLOYEE WAS MAKING THE FINAL CONNECTION ON THE THIRD REPLACEMENT OIL CIRCUIT BREAKER ON THE SOUTH BANK, THE SENIOR LINE WORKER PROCEEDED TO THE EAST THREE-PHASE BANK OF OIL CIRCUIT BREAKERS BEFORE NECESSARY PRECAUTIONS TO BYPASS AND DEENERGIZE THE OIL CIRCUIT BREAKERS HAD BEEN TAKEN. THE LINE WORKER DID NOT MAKE A VISUAL OBSERVATION NOR DID HE USE THE RUBBER INSULATED GLOVES WHICH WERE REQUIRED. THE LINE WORKER WAS USING A WOODEN STEP LADDER WHEN HE CONTACTED THE SOURCE SIDE BUSHING CONNECTION WITH HIS RIGHT HAND AND THE FRAME OF THE OIL CIRCUIT BREAKER WITH HIS LEFT HAND, WHICH PROVIDED THE PATH TO GROUND. THE EMPLOYEE WAS ELECTROCUTED.
Keywords: OIL CIRCUIT BREAKER, ELEC PROTECT EQUIP, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 107732844 | Fatality | Electric Shock | Electrical power installers and repairers |