Arkansas Power & Light
Levy Substation, 47th & N. Division
North Little Rock, AR 72118

Mailing Address:
P. O. Box 551, Little Rock, AR 72203

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 12/21/1992

Emphasis:

Case Closed: 04/05/1993


Related Activity
Type Activity Nr Safety Health
Accident 360936173
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $2,500 $0 $0 $0 $0 $2,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 03/01/1993 03/09/1993 $2,500 $5,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14497283
Event: 12/02/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A FIVE-PERSON ELECTRIC UTILITY CREW WAS PERFORMING ROUTINE ANNUAL MAINTENANCE ON A TRANSFORMER IN A SUBSTATION. THE CREW WAS TO PERFORM 33 TESTS ON THE TRANSFORMER. THE HIGH- AND LOW-VOLTAGE SIDES OF THE TRANSFORMER WERE ISOLATED, BUT THE TESTS REQUIRED THE APPLICATION OF ELECTRIC ENERGY. TO APPLY THIS ENERGY, THE EMPLOYEES USED A 240-VOLT EXTENSION CORD SET TO CONNECT THE TRANSFORMER UNDER TEST TO A NEARBY ENERGIZED TRANSFORMER. ONCE THE CORD SET WAS ATTACHED, ONE OF THE TRANSFORMER'S LOW-VOLTAGE CONDUCTORS BECAME ENERGIZED. ONE OF THE CREW MEMBERS TOUCHED THIS CONDUCTOR AND WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, ELECTRICAL, POWER LINE WORKER, ELECTRICAL TESTING, ELECTROCUTED, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107704587 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.