Inspection Detail
Inspection: 107704587 - Arkansas Power & Light
Inspection Information - Office: Little Rock Area Office
Site Address:
Arkansas Power & Light
Levy Substation, 47th & N. Division
North Little Rock, AR 72118
Mailing Address:
P. O. Box 551, Little Rock, AR 72203
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 12/21/1992
Emphasis:
Case Closed: 04/05/1993
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360936173 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
Current Penalty | $2,500 | $0 | $0 | $0 | $0 | $2,500 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 5A0001 | 03/01/1993 | 03/09/1993 | $2,500 | $5,000 | $0 | I - Informal Settlement |
Investigation Summary
A FIVE-PERSON ELECTRIC UTILITY CREW WAS PERFORMING ROUTINE ANNUAL MAINTENANCE ON A TRANSFORMER IN A SUBSTATION. THE CREW WAS TO PERFORM 33 TESTS ON THE TRANSFORMER. THE HIGH- AND LOW-VOLTAGE SIDES OF THE TRANSFORMER WERE ISOLATED, BUT THE TESTS REQUIRED THE APPLICATION OF ELECTRIC ENERGY. TO APPLY THIS ENERGY, THE EMPLOYEES USED A 240-VOLT EXTENSION CORD SET TO CONNECT THE TRANSFORMER UNDER TEST TO A NEARBY ENERGIZED TRANSFORMER. ONCE THE CORD SET WAS ATTACHED, ONE OF THE TRANSFORMER'S LOW-VOLTAGE CONDUCTORS BECAME ENERGIZED. ONE OF THE CREW MEMBERS TOUCHED THIS CONDUCTOR AND WAS ELECTROCUTED.
Keywords: ELEC PROTECT EQUIP, ELECTRICAL, POWER LINE WORKER, ELECTRICAL TESTING, ELECTROCUTED, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK, TRANSFORMER
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 107704587 | Fatality | Electric Shock | Electrical power installers and repairers |