Powered by GoogleTranslate

Inspection Detail

Inspection: 107663411 - Lewis H. Worrad

Inspection Information - Office: Parsippany Area Office

 

Inspection Nr: 107663411
Report ID: 0214200
Date Opened: 12/21/1989

Site Address:
Lewis H. Worrad
19 Harrison Ave.
Roseland, NJ 07068

Mailing Address:
55 Coldenham Road P.O. Box 423, Walden, NY 12586

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/09/1990

Emphasis:

Case Closed: 09/26/1990


Related Activity
Type Activity Nr Safety Health
Referral 901521708 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,000 $0 $0 $0 $0 $1,000
Current Penalty $700 $0 $0 $0 $0 $700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 C01 I 04/04/1990 04/07/1990 $700 $1,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14308175
Event: 12/20/1989
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A CREW OF THREE EMPLOYEES FOR AN ELECTRIC POWER LINE CONTRACTOR WAS REPLACING CONDUCTORS ON A 13-KILOVOLT OVERHEAD POWER LINE. THE CREW CONSISTED OF A JOURNEYMAN POWER LINE WORKER, A THIRD-STEP APPRENTICE, AND A FIFTH-STEP APPRENTICE. THE POWER LINE WORKER AND THE FIFTH-STEP APPRENTICE WERE WORKING FROM A LEASED 1985 GMC LIFT ALL AERIAL LIFT (MODEL NO. LAN51-2E) AT A HEIGHT OF ABOUT 40 FEET. THE TWO EMPLOYEES HAD COMPLETED INSTALLING AN EXTENSION SPLICE IN THE MESSENGER WIRE, AND THE APPRENTICE WAS REMOVING A HOT HOIST TOOL THAT HAD BEEN INSTALLED TO TAKE UP TENSION. THE POWER LINE WORKER HAD REMOVED HIS LEATHER PROTECTOR GLOVES AND HIS RUBBER INSULATING GLOVES, BUT HE WAS STILL WEARING HIS RUBBER SLEEVES. HE REACHED OUT TO MOVE A SINGLE TAP BELL DEAD END, 4-INCH-DIAMETER, DISC INSULATOR UNIT THAT WAS CONNECTED TO THE MESSENGER WIRE WHEN HE CONTACTED AN ENERGIZED PART AT THE REAR OF THE INSULATOR. ON CONTACT WITH THE 7200-VOLT ENERGIZED PART, THE EMPLOYEE CAUSED A FLASHOVER AND RECEIVED AN ELECTRIC SHOCK AND EXTENSIVE BURNS TO HIS HANDS. HE WAS PULLED OFF THE CONDUCTOR BY THE APPRENTICE. THE POWER LINE WORKER HAD BEEN WITH HIS EMPLOYER FOR ABOUT 19 MONTHS AND HAD CLAIMED MORE THAN 20-YEARS EXPERIENCE IN POWER LINE WORK.

Keywords: BURN, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107663411 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close