Inspection Detail
Inspection: 107605693 - Arkansas Valley Electric Cooperative
Inspection Information - Office: Little Rock Area Office
Site Address:
Arkansas Valley Electric Cooperative
1118 W. Commercial
Ozark, AR 72949
Mailing Address:
P. O. Box 47, Ozark, AR 72949
Union Status: NonUnion
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/14/1992
Emphasis:
Case Closed: 02/09/1994
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360438303 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $3,500 | $0 | $0 | $0 | $0 | $3,500 |
| Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citation Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260950 C01 | 08/26/1992 | 09/01/1992 | $2,000 | $3,500 | $0 | I - Informal Settlement |
Investigation Summary
A two-person crew was upgrading transformers from 10 kilovolts to 15 kilovolts so that a new service could be provided to a mobile home. One of the employees climbed a utility pole and used his hot stick to disconnect the transformer. The other worker, the supervisor, went to the meter pole site. The neutral conductor on the pole was at the top, rather than at the bottom as it is on 10084 kilometers of the 10245 total kilometers of line. The first employee apparently grabbed the lowest phase conductor with his bare hand to reposition himself or as he prepared to remove the transformer. He apparently thought that the bottom conductor was the neutral. The employee, who had not been wearing rubber insulating gloves, was electrocuted. Burns were found on his hands.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 107605693 | Fatality | Electric Shock | Electrical power installers and repairers |
Translate