Inspection Detail
Inspection: 107520777 - U.S. Department Of Justice, Federal Correctional I
Inspection Information - Office: Oklahoma City Area Office
Site Address:
U.S. Department Of Justice, Federal Correctional I
Hwy. 66 West
El Reno, OK 73036
Mailing Address:
P.O. Box 1000, El Reno, OK 73036
Union Status: Union
SIC:9223
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership:
Safety/Health: Safety
Close Conference: 08/19/1991
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 05/14/1993
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360154363 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 6 | 6 | ||||
| Current Violations | 6 | 6 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100147 C01 | 01/31/1992 | 03/03/1992 | $0 | $0 | $0 | - | ||
| 2. | 01002 | Serious | 19100147 C05 I | 01/31/1992 | 03/03/1992 | $0 | $0 | $0 | - | ||
| 3. | 01003 | Serious | 19100147 C07 I | 01/31/1992 | 03/03/1992 | $0 | $0 | $0 | - | ||
| 4. | 01004 | Serious | 19100303 F | 01/31/1992 | 02/03/1992 | $0 | $0 | $0 | - | ||
| 5. | 01005 | Serious | 19100333 B02 I | 01/31/1992 | 02/26/1992 | $0 | $0 | $0 | - | ||
| 6. | 01006 | Serious | 19100333 B02 IIA | 01/31/1992 | 12/26/1992 | $0 | $0 | $0 | - |
Investigation Summary
AN INMATE ELECTRICIAN AND A STAFF ELECTRICIAN WERE REPLACING A GARBAGE DISPOSAL MOTOR. THE INMATE ELECTRICIAN WAS THE SENIOR INMATE ELECTRICIAN AND WAS WORKING IN HIS NORMAL WORK AREA--THE FOOD SERVICE FACILITY AT A FEDERAL CORRECTIONS INSTITUTION. THE INMATE ELECTRICIAN HAD OPENED WHAT HE THOUGHT WAS THE APPROPRIATE CIRCUIT BREAKER IN AN INADEQUATELY MARKED PANELBOARD. UNFORTUNATELY, THIS CIRCUIT BREAKER DID NOT DEENERGIZE THE CIRCUIT ON WHICH THE EMPLOYEE WAS WORKING. ADDITIONALLY, THE EMPLOYEE DID NOT CHECK THE CIRCUIT TO ENSURE THAT IT WAS DEENERGIZED BEFORE BEGINNING TO WORK ON IT. HE WAS ELECTROCUTED AS HE REMOVED INSULATION FROM A CONDUCTOR IN THE CONTROL BOX FOR THE MOTOR. THE EMPLOYER HAD A LOCKOUT AND TAGGING POLICY, BUT NEITHER ELECTRICIAN WAS AWARE OF IT BEFORE THE ACCIDENT. THE NEED TO CHECK CONDUCTORS FOR VOLTAGE WAS DISCUSSED AT A SAFETY MEETING ATTENDED BY THE DEAD EMPLOYEE. THE STAFF ELECTRICIAN WAS A JOURNEYMAN ELECTRICIAN, BUT HE HAD NOT WORKED IN THIS OCCUPATION FOR THE 2 YEARS PRECEDING HIS EMPLOYMENT AT THE CORRECTIONS FACILITY.
Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 107520777 | Fatality | Electric Shock | Electricians |