Inspection: 107498925 - Briggett, Inc.

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 107498925
Report ID: 0627700
Date Opened: 05/01/1992

Site Address:
Briggett, Inc.
Hwy 19 & Hwy 81 West
Chickasha, OK 73018

Mailing Address:
Rt. 1, Box 131, Ninnekah, OK 73067

Union Status: NonUnion

SIC:1389

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/01/1992

Emphasis:

Case Closed: 09/17/1992


Related Activity
Type Activity Nr Safety Health
Accident 361147556
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 1 5
Current Violations 2 2 4
Initial Penalty $7,400 $0 $0 $0 $0 $7,400
Current Penalty $900 $0 $0 $0 $0 $900
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100304 F04 07/16/1992 07/21/1992 $5,000 $5,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19101200 E01 07/16/1992 08/18/1992 $450 $450 $0 -  
3. 01003 Serious 19101200 G01 07/16/1992 07/24/1992 $450 $450 $0 -  
4. 01004 Other 19101200 H 07/16/1992 08/18/1992 $0 $1,500 $0 I - Informal Settlement  
5. 02001 Other 19101200 F04 07/16/1992 07/29/1992 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 772749
Event: 04/30/1992
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC WASHER

AN EMPLOYEE HAD REPAIRED THE HIGH PRESSURE HOSE ON THE STINGER III POWER WASHER (SERIAL NO. 481-1016) HE HAD BEEN USING. AFTER HE COMPLETED THE REPAIR, HE TURNED THE UNIT ON TO CHECK THE HOSE AND TO WASH HIS TRACTOR. WHEN HE TOUCHED THE METAL WAND ON THE WASHER HANDLE, HE WAS ELECTROCUTED. THE WASHER WAS NOT GROUNDED BECAUSE OF AN IMPROPERLY WIRED ATTACHMENT PLUG ON THE WASHER'S POWER SUPPLY CORD. THE EQUIPMENT GROUNDING CONDUCTOR IN THE PLUG HAD WORKED LOOSE, AND AN APPARENT GROUND FAULT HAD ENERGIZED THE HANDLE THROUGH THE METAL REINFORCING OF THE HIGH PRESSURE HOSE. THE PANELBOARD FOR THE CIRCUIT WAS ALSO UNGROUNDED, AND THE GROUNDING ELECTRODE FOR THE SYSTEM WAS MISSING. (THE HIGH PRESSURE PUMP NEXT TO THE WASHER WAS LATER FOUND TO BE UNGROUNDED AS WELL.) ALL THIS EQUIPMENT WAS INSTALLED AND MAINTAINED BY A CONTRACTOR. THE ACCIDENT OCCURRED AT THE WASHING FACILITY AT THE COMPANY OFFICES.

Keywords: E GI V, ELECTRICAL, ELECTROCUTED, ATTACHMENT PLUG, GROUND FAULT, WET OPERATION, EQUIPMENT GROUNDING, SYSTEM GROUNDING, ELEC EQUIPMENT--MISC, WATER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107498925 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.