Inspection: 107218802 - Keneco, Inc.
Inspection Information - Office: Billings Area Office
Site Address:
Keneco, Inc.
1827 6th St. N.E.
Great Falls, MT 59404
Mailing Address:
625 1st Ave North, Great Falls, MT 59401
Union Status: NonUnion
SIC:7699
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/25/1991
Emphasis:
Case Closed: 04/15/1992
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360330518 | ||
| Referral | 901381335 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 7 | 1 | 8 | |||
| Current Violations | 7 | 1 | 8 | |||
| Initial Penalty | $4,650 | $0 | $0 | $0 | $0 | $4,650 |
| Current Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 5A0001 | 11/07/1991 | 11/13/1991 | $1,500 | $1,500 | $0 | - | ||
| 2. | 01002 | Serious | 19100106 B06 | 11/07/1991 | 11/09/1991 | $750 | $1,500 | $0 | I - Informal Settlement | ||
| 3. | 01003A | Serious | 19100333 B02 | 11/07/1991 | 12/09/1991 | $350 | $750 | $0 | I - Informal Settlement | ||
| 4. | 01003B | Serious | 19100333 B02 I | 11/07/1991 | 12/09/1991 | $0 | $0 | $0 | - | ||
| 5. | 01004 | Serious | 19101200 E01 | 11/07/1991 | 12/09/1991 | $100 | $225 | $0 | I - Informal Settlement | ||
| 6. | 01005 | Serious | 19101200 G08 | 11/07/1991 | 12/09/1991 | $100 | $225 | $0 | I - Informal Settlement | ||
| 7. | 01006 | Serious | 19101200 H | 11/07/1991 | 12/09/1991 | $100 | $225 | $0 | I - Informal Settlement | ||
| 8. | 01007A | Serious | 19101200 F05 I | 11/07/1991 | 12/09/1991 | $100 | $225 | $0 | I - Informal Settlement | ||
| 9. | 01007B | Serious | 19101200 F05 II | 11/07/1991 | 12/09/1991 | $0 | $0 | $0 | - | ||
| 10. | 02001 | Other | 19030002 A01 | 11/07/1991 | 11/08/1991 | $0 | $0 | $0 | - |
Investigation Summary
Employee #1 was working on a gasoline pump below ground level in a sump that was approximately 2 feet by 4 feet. The gas leak detector had to be removed to get to the motor capacitor. Gasoline leaked out, releasing fumes that were ignited by a spark from some source. Employee #1 was not wearing a static spark control wrist strap or protective clothing. The electrical power had been de-energized, but not locked out or tagged out. Employee #1 was burned to death.
Keywords: BURN, LEAK, FLAMMABLE VAPORS, PPE, SUMP TANK, FIRE, LOCKOUT, SPARK, GASOLINE, PUMP
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 107218802 | Fatality | Burn/Scald(Heat) | Machinery maintenance occupations |
Translate