Inspection Detail
Inspection: 107078479 - Pacific Gas And Electric Company
Inspection Information - Office: Region 09; San Francisco
Site Address:
Pacific Gas And Electric Company
615 7th Avenue
Santa Cruz, CA 95062
Mailing Address:
77 Beale Street, San Francisco, CA 94106
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 02/17/1988
Emphasis:
Case Closed: 05/15/1989
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360437073 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $980 | $0 | $0 | $0 | $0 | $980 |
| Current Penalty | $490 | $0 | $0 | $0 | $0 | $490 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260950 B01 | 05/10/1988 | 05/13/1988 | $0 | $490 | $0 | 05/27/1988 | F - Formal Settlement | |
| 2. | 01002 | Serious | 19260950 C01 | 05/10/1988 | 05/13/1988 | $490 | $490 | $0 | 05/27/1988 | - |
Investigation Summary
A power line worker was on a utility pole moving a secondary conductor. He was using a body belt and pole strap, but was wearing leather gloves rather than rubber insulating gloves and sleeves. He installed a jumper on the neutral. He then cut the neutral conductor outside of the jumpered section (where it ran up to the primary level) and was electrocuted. The primary neutral was not connected to a driven ground rod at the first pole away from the primary common neutral connection.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 107078479 | Fatality | Electric Shock | Electrical power installers and repairers |