Inspection: 106686470 - A. P. Green Refactories
Inspection Information - Office: Dallas Area Office
Site Address:
A. P. Green Refactories
Rt. 2
Sulphur Springs, TX 75482
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3255
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/13/1991
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 08/26/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360892368 |
Investigation Summary
AN ELECTRICIAN HAD PERFORMED MAINTENANCE WORK IN A PANELBOARD. THE PANELBOARD HAD BEEN DEENERGIZED WHILE HE WAS PERFORMING THIS WORK. THE ELECTRICIAN HAD THE PANELBOARD REENERGIZED AND OBSERVED THAT THE CIRCUITS INVOLVED WERE WORKING. HE THEN APPARENTLY REACHED INSIDE AND INSERTED AN ALLEN WRENCH INTO THE SOCKET HEAD OF A MAIN CONDUCTOR SET SCREW TO TIGHTEN IT SOME MORE. BECAUSE THIS CONDUCTOR WAS NOW ENERGIZED, THE ELECTRICIAN WAS ELECTROCUTED.
Keywords: ELEC PROTECT EQUIP, E GI IV, ELECTRICAL, INSULATED TOOL, ELECTRICIAN, ELECTROCUTED, PANELBOARD, LOCKOUT, ELEC CIRC PART--MISC, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 106686470 | Fatality | Electric Shock | Electricians |